          Short circuit protection with MO132 for group mounting, IEC Type 1, 500 V AC, EN/IEC 60947-4-2
          Max. sum of current of HF-Starter in group  Iq  HF-Starter Type  SCPD
                                   kA                                      A
          6.5                      35               DOL, ROL, DOLE, ROLE (1)  MO132-6.3
          10                       3                                       MO132-10
          12                       3                                       MO132-12
          16                       3                                       MO132-16
          20                       3                                       MO132-20
          25                       3                                       MO132-25
          32                       3                                       MO132-32
          (1) HF9 is able to switch 9A in AC-51, 6.5A in AC-53a

          Short circuit protection with MO132 for group mounting, IEC Type 1, 415 V AC, EN/IEC 60947-4-2
          Max. sum of current of HF-Starter in group  Iq  HF-Starter Type  SCPD
                                   kA                                      A
          6.5                      70               DOL, ROL, DOLE, ROLE (1)  MO132-6.3
          10                       35                                      MO132-10
          12                       3                                       MO132-12
          16                       3                                       MO132-16
          20                       3                                       MO132-20
          25                       3                                       MO132-25
          32                       3                                       MO132-32
          (1) HF9 is able to switch 9A in AC-51, 6.5A in AC-53a

          Single mounting fused design, IEC Type 1, 500 V AC, 35 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
          Rated motor power  Rated motor current  Starter Type  Protection type  HF-Starter  Current setting range    Max. allowed setting
                                                                                   of HF-Starter  current for AC-53a
          kW           A                                                           A             A
          0.18         0.48         DOL, ROL, DOLE, ROLE (1)  Fuse 25A gG  HF0.6   0.075 - 0.6   0.6
          1.1          2.2          DOL, ROL, DOLE, ROLE (1)  Fuse 25A gG  HF2.4   0.18 - 2.4    2.4
          3.0          5.2          DOL, ROL, DOLE, ROLE, R (1)  Fuse 25A gG  HF9  1.5 - 91)     6.5
          (1) HF9 variants can switch 6.5A in utilization category AC-53a and 9A in AC-51.

          Single mounting fused design, IEC Type 1, 415 V AC, 50 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
          Rated motor power  Rated motor current  Starter Type  Protection type  HF-Starter  Current setting range    Max. allowed setting
                                                                                   of HF-Starter  current for AC-53a
          kW           A                                                           A             A
          0.18         0.58         DOL, ROL, DOLE, ROLE (1)  Fuse 25A gG  HF0.6   0.075 - 0.6   0.6
          0.75         1.8          DOL, ROL, DOLE, ROLE (1)  Fuse 25A gG  HF2.4   0.18 - 2.4    2.4
          3.0          6.3          DOL, ROL, DOLE, ROLE (1)  Fuse 25A gG  HF9     1.5 - 91)     6.5                  11
          (1) HF9 variants can switch 6.5A in utilization category AC-53a and 9A in AC-51.

          Group mounting fused design, IEC Type 1, 500 V AC, 35 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
          Iq           SCPD         Max. sum of current of used devices  HF-Starter

          kA                        A
          35           Fuse 25A gG  25                     HF0.6
          35           Fuse 25A gG  25                     HF2.4
          35           Fuse 25A gG  25                     HF9

          Group mounting fused design, IEC Type 1, 415 V AC, 50 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
          Iq           SCPD         Max. sum of current of used devices  HF-Starter

          kA                        A
          50           Fuse 25A gG  25                     HF0.6
          50           Fuse 25A gG  25                     HF2.4
          50           Fuse 25A gG  25                     HF9