Page 849 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 849
ABB MOTOR PROTECTION AND CONTROL 11/11
—
HF0.6, HF2.4, HF9 electronic compact starters
Technical data
Short circuit protection with MO132 for group mounting, IEC Type 1, 500 V AC, EN/IEC 60947-4-2
Max. sum of current of HF-Starter in group Iq HF-Starter Type SCPD
kA A
6.5 35 DOL, ROL, DOLE, ROLE (1) MO132-6.3
10 3 MO132-10
12 3 MO132-12
16 3 MO132-16
20 3 MO132-20
25 3 MO132-25
32 3 MO132-32
(1) HF9 is able to switch 9A in AC-51, 6.5A in AC-53a
Short circuit protection with MO132 for group mounting, IEC Type 1, 415 V AC, EN/IEC 60947-4-2
Max. sum of current of HF-Starter in group Iq HF-Starter Type SCPD
kA A
6.5 70 DOL, ROL, DOLE, ROLE (1) MO132-6.3
10 35 MO132-10
12 3 MO132-12
16 3 MO132-16
20 3 MO132-20
25 3 MO132-25
32 3 MO132-32
(1) HF9 is able to switch 9A in AC-51, 6.5A in AC-53a
Single mounting fused design, IEC Type 1, 500 V AC, 35 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
Rated motor power Rated motor current Starter Type Protection type HF-Starter Current setting range Max. allowed setting
of HF-Starter current for AC-53a
kW A A A
0.18 0.48 DOL, ROL, DOLE, ROLE (1) Fuse 25A gG HF0.6 0.075 - 0.6 0.6
1.1 2.2 DOL, ROL, DOLE, ROLE (1) Fuse 25A gG HF2.4 0.18 - 2.4 2.4
3.0 5.2 DOL, ROL, DOLE, ROLE, R (1) Fuse 25A gG HF9 1.5 - 91) 6.5
(1) HF9 variants can switch 6.5A in utilization category AC-53a and 9A in AC-51.
Single mounting fused design, IEC Type 1, 415 V AC, 50 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
Rated motor power Rated motor current Starter Type Protection type HF-Starter Current setting range Max. allowed setting
of HF-Starter current for AC-53a
kW A A A
0.18 0.58 DOL, ROL, DOLE, ROLE (1) Fuse 25A gG HF0.6 0.075 - 0.6 0.6
0.75 1.8 DOL, ROL, DOLE, ROLE (1) Fuse 25A gG HF2.4 0.18 - 2.4 2.4
3.0 6.3 DOL, ROL, DOLE, ROLE (1) Fuse 25A gG HF9 1.5 - 91) 6.5 11
(1) HF9 variants can switch 6.5A in utilization category AC-53a and 9A in AC-51.
Group mounting fused design, IEC Type 1, 500 V AC, 35 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
Iq SCPD Max. sum of current of used devices HF-Starter
kA A
35 Fuse 25A gG 25 HF0.6
35 Fuse 25A gG 25 HF2.4
35 Fuse 25A gG 25 HF9
Group mounting fused design, IEC Type 1, 415 V AC, 50 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
Iq SCPD Max. sum of current of used devices HF-Starter
kA A
50 Fuse 25A gG 25 HF0.6
50 Fuse 25A gG 25 HF2.4
50 Fuse 25A gG 25 HF9