Page 851 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 851

ABB  MOTOR PROTECTION AND CONTROL                                                11/13

          —

          HF0.6, HF2.4, HF9 electronic compact starters
          Technical data




          Safety related data
          Type                                  HF-DOLE/ROLE
          Standards                             IEC/EN 60947-1, IEC/EN 60947-4-2, IEC/EN 61508, IS0 13849
          Safe shut down for ambient temperature 40°C … 60°C
            Safety integrity level acc. to  IEC 61508-1  SIL 3
            Performance level                   Up to e
            Mean time to failure (MTTF) acc. to IEC60050-191-12-07  DOLE: 43 years
                                                ROLE: 39.3 years
            Mean time to dangerous failure, motor protection  447 years
            Mean time to dangerous failure, safe shutdown  DOLE: 518 years
                                                ROLE: 517 years
            Failure in time  Safe, detectabled λsd  DOLE:  543 FIT
                                                ROLE: 664 FIT
                          Safe, undetectable λsu  DOLE:  852 FIT
                                                ROLE: 968 FIT
                          Dangerous, detectable λdd  218 FIT
                          Dangerous, undetectable λdu  DOLE:  2.4 FIT
                                                ROLE: 2.67 FIT
            Safe failure fraction (SFF)         DOLE:  99.85%
                                                ROLE: 99.86%
            Diagnostic coverage (DC)            DOLE: 98.91%
                                                ROLE: 98.79%
            Probability of dangerous failure per hour (PFH)  DOLE: 2.4
                                                ROLE: 2.67
          Motor overload protection for ambient temperature 40°C … 60°C
            Safety integrity level acc. to  IEC 61508-1  SIL 3
            Performance level                   Up to e
            Mean time to failure (MTTF) acc. to IEC60050-191-12-07  DOLE: 43 years
                                                ROLE: 39.3 years
            Mean time to dangerous failure, safe shutdown  DOLE: 518 years
                                                ROLE: 517 years
            Failure in time  Safe, detectabled  DOLE:  517 FIT
                                                ROLE: 637 FIT
                          Safe, undetectable    DOLE:  809 FIT
                                                ROLE: 870 FIT
                          Dangerous, detectable  239 FIT
                          Dangerous, undetectable  17 FIT
            Safe failure fraction (SFF)         DOLE:  98.92%
                                                ROLE: 99.03%
            Diagnostic coverage                 DOLE: 98.91%
                                                ROLE: 98.79%

                                                                                                                      11
   846   847   848   849   850   851   852   853   854   855   856