Page 848 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 848
11/10 ABB MOTOR PROTECTION AND CONTROL
—
HF0.6, HF2.4, HF9 electronic compact starters
Technical data
Main circuit – Utilization characteristics according to IEC/EN
Type HF-DOL/ROL HF-DOLE/ROLE
Standards IEC/EN 60947-1, IEC/EN 60947-4-2 IEC/EN 60947-1, IEC/EN 60947-4-2, IEC/EN 61508, IS0
13849
Rated operational voltage Ue 500 V AC
Operational Minimum 42 V AC,
voltage Maximum 550 V AC
Setting range see ordering details
Rated frequency 50/60 Hz
Trip class 10A
Number of poles 3
Number of protected poles 3
Mechanical durability 10000 cycles
Electrical durability 30 Mio. cycles
Rated impulse withstand voltage Uimp 6 kV
Rated insulation voltage Ui 500 V
Rated operational current Ie AC-51 see ordering details
Rated operational current Ie AC-53a see ordering details
Rated uninterrupted current Iu see ordering details, Rated operational current Ie
Overvoltage category III
Delay time Off, minimum, switched off with pushbutton 1 s 1 s
Off, maximum, switched off with pushbutton 3 s 3 s
Off, typical, switched off via control input voltage 30 ms 30 ms
Off, maximum, switched off via control input - HF0.6, HF2.4: 60 ms
voltage HF9: 80 ms
Off, typical, switched off via supply voltage 25 ms 25 ms
Off, maximum, switched off via supply voltage - 500 ms
Switch off By phase failure 1.8 s 1.8 s
time By phase asymmetry at 33% 120 s 120 s
By phase asymmetry at 67% 1.8 s 1.8 s
Overspeed Operating threshold HF9-DOL/ROL/DOLE/ROLE: >45 A
tripping Response time HF9-DOL/ROL/DOLE/ROLE: 2 s
Power loss Minimum 1.1 W
Maximum HF0.6: 1.5 W
HF2.4: 3.3 W
HF9: 14.6 W
Switching frequency ≤ 2 Hz; 120 starts/min; 7200 starts/h
Overvoltage category III
Short circuit protection with MO132 for single mounting, IEC Type 1, 500 V AC, 35 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
Rated motor power Rated motor current Starter Type Protection type HF-Starter Current setting range Max. allowed setting
of HF-Starter current for AC-53a
11
kW A A A
0.18 0.48 DOL, ROL, DOLE, ROLE (1) MO132-0.63 HF0.6 0.075 - 0.6 0.6
1.1 2.2 DOL, ROL, DOLE, ROLE (1) MO132-2.5 HF2.4 0.18 - 2.4 2.4
3.0 5.2 DOL, ROL, DOLE, ROLE (1) MO132-6.3 HF9 1.5 - 9 (1) 6.5
(1) HF9 is able to switch 9A in AC-51, 6.5A in AC-53a.
Short circuit protection with MO132 for single mounting, IEC Type 1, 415 V AC, 70 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
Rated motor power Rated motor current Starter Type Protection type HF-Starter Current setting range Max. allowed setting
of HF-Starter current for AC-53a
kW A A A
0.18 0.58 DOL, ROL, DOLE, ROLE (1) MO132-0.63 HF0.6 0.075 - 0.6 0.6
0.75 1.8 DOL, ROL, DOLE, ROLE (1) MO132-2.5 HF2.4 0.18 - 2.4 2.4
3.0 6.3 DOL, ROL, DOLE, ROLE (1) MO132-6.3 HF9 1.5 - 9 (1) 6.5
(1) HF9 is able to switch 9A in AC-51, 6.5A in AC-53a