Page 848 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 848

11/10            ABB  MOTOR PROTECTION AND CONTROL

          —

          HF0.6, HF2.4, HF9 electronic compact starters
          Technical data




          Main circuit – Utilization characteristics according to IEC/EN
          Type                               HF-DOL/ROL                       HF-DOLE/ROLE
          Standards                          IEC/EN 60947-1, IEC/EN 60947-4-2  IEC/EN 60947-1, IEC/EN 60947-4-2, IEC/EN 61508, IS0
                                                                              13849
          Rated operational voltage Ue       500 V AC
          Operational  Minimum               42 V AC,
          voltage  Maximum                   550 V AC
          Setting range                      see ordering details
          Rated frequency                    50/60 Hz
          Trip class                         10A
          Number of poles                    3
          Number of protected poles          3
          Mechanical durability              10000 cycles
          Electrical durability              30 Mio. cycles
          Rated impulse withstand voltage Uimp  6 kV
          Rated insulation voltage Ui        500 V
          Rated operational current Ie AC-51  see ordering details
          Rated operational current Ie AC-53a  see ordering details
          Rated uninterrupted current Iu     see ordering details, Rated operational current Ie
          Overvoltage category               III
          Delay time Off, minimum, switched off with pushbutton  1 s          1 s
                Off, maximum, switched off with pushbutton  3 s               3 s
                Off, typical, switched off via control input voltage 30 ms    30 ms
                Off, maximum, switched off via control input   -              HF0.6, HF2.4: 60 ms
                voltage                                                       HF9: 80 ms
                Off, typical, switched off via supply voltage  25 ms          25 ms
                Off, maximum, switched off via supply voltage  -              500 ms
          Switch off  By phase failure       1.8 s                            1.8 s
          time  By phase asymmetry at 33%    120 s                            120 s
                By phase asymmetry at 67%    1.8 s                            1.8 s
          Overspeed  Operating threshold     HF9-DOL/ROL/DOLE/ROLE: >45 A
          tripping  Response time            HF9-DOL/ROL/DOLE/ROLE: 2 s
          Power loss  Minimum                1.1 W
                Maximum                      HF0.6: 1.5 W
                                             HF2.4: 3.3 W
                                             HF9: 14.6 W
          Switching frequency                ≤ 2 Hz; 120 starts/min; 7200 starts/h
          Overvoltage category               III
          Short circuit protection with MO132 for single mounting, IEC Type 1, 500 V AC, 35 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
          Rated motor power  Rated motor current  Starter Type  Protection type  HF-Starter  Current setting range    Max. allowed setting
                                                                                   of HF-Starter  current for AC-53a
   11
          kW           A                                                           A             A
          0.18         0.48         DOL, ROL, DOLE, ROLE (1)  MO132-0.63  HF0.6    0.075 - 0.6   0.6
          1.1          2.2          DOL, ROL, DOLE, ROLE (1)  MO132-2.5  HF2.4     0.18 - 2.4    2.4
          3.0          5.2          DOL, ROL, DOLE, ROLE (1)  MO132-6.3  HF9       1.5 - 9 (1)   6.5
          (1) HF9 is able to switch 9A in AC-51, 6.5A in AC-53a.
          Short circuit protection with MO132 for single mounting, IEC Type 1, 415 V AC, 70 kA, 50 Hz, AC-53a, EN/IEC 60947-4-2
          Rated motor power  Rated motor current  Starter Type  Protection type  HF-Starter  Current setting range    Max. allowed setting
                                                                                   of HF-Starter  current for AC-53a
          kW           A                                                           A             A
          0.18         0.58         DOL, ROL, DOLE, ROLE (1)  MO132-0.63  HF0.6    0.075 - 0.6   0.6
          0.75         1.8          DOL, ROL, DOLE, ROLE (1)  MO132-2.5  HF2.4     0.18 - 2.4    2.4
          3.0          6.3          DOL, ROL, DOLE, ROLE (1)  MO132-6.3  HF9       1.5 - 9 (1)   6.5
          (1) HF9 is able to switch 9A in AC-51, 6.5A in AC-53a