11/12            ABB  MOTOR PROTECTION AND CONTROL

          —

          HF0.6, HF2.4, HF9 electronic compact starters
          Technical data




          Main circuit – Utilization characteristics according to UL/CSA
          Type                               HF
          Standards                          UL 60947-1; UL 60947-4-2
          Rated operational voltage          500 V AC
          Operational voltage Minimum        42 V AC
                      Maximum                550 V AC
          Ampere Rating UL/CSA               see ordering details, Full load amps motor use
          Horse power rating  Nominal switching performance full load   HF0.6: 0.4 hp
                      (power factor = 0.4)   HF2.4: 1.2 hp
                                             HF9: 3.0 hp
                      Nominal switching performance full load   HF0.6: 0.6 hp
                      (power factor = 0.8)   HF2.4: 2.2 hp
                                             HF9: 6.1 hp
          Full loads Amps (FLA)              see ordering details
          Short-circuit current rating (SCCR) (500 V AC, 30 A Class J or CC) 100 kA



          General technical data
          Type                               HF
          Utilization category               AC51, AC53a
          Pollution degree                   2
          Phase loss sensitive               Yes
          Ambient air temperature Operation  -25 ... + 70 °C
                        Operation compensated  -40 ... + 80 °C
          Mounting position                  Position 1,  load side bottom
          Mounting in DIN Rail               TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715,
                                             TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
          Degree of protection  Housing      IP20
                        Main circuit terminals  IP20


          Control circuit
          Type                               HF
          Rated control circuit voltage Uc   24 V DC
          Input voltage Uin  Switching Threshold at Signal <0>  -3 ... 9.6 V
                       Switching Threshold at Signal <1>  19.2 ... 30 V
          Input current Ic                   3 mA


          Supply circuit
   11
          Type                               HF
          Rated control supply voltage Us    24 V DC
          Control supply voltage             19.2 ... 30 V DC
          Rated control supply current Is    0.04 A

          Single and group mounting HF-Starter, Type 1 coordination with fuse class J or CC according to UL60947-1/-4-1
          HF-Starter       FLA              Iq               SCPD             Max. current     Max. Voltage
                           A / V AC         kA                                A                V AC
          HF0.6            0.6 / 500        100              Fuse class J or CC  30            480
          HF2.4            2.4 / 500        100              Fuse class J or CC  30            480
          HF9              6.5 / 500        100              Fuse class J or CC  30            480

          Single and group mounting HF-Starter, Type 1 coordination with fuse RK 5 according to UL60947-1/-4-1
          HF-Starter       FLA              Iq               SCPD             Max. current     Max. Voltage

                           A / V AC         kA                                A                V AC
          HF0.6            0.6 / 500        5                Fuse RK 5        20               480
          HF2.4            2.4 / 500        5                Fuse RK 5        20               480
          HF9              6.5 / 500        5                Fuse RK 5        20               480