Page 2205 - Din prodcuts 2020
P. 2205
15/81
—
ABB-free@home®
DINRail
Fan Coil Actuator, PWM, MDRC
For controlling blower convectors.
Supports 2-pipe and 4-pipe system for heating and cooling.
The fan speed levels can be switched using a changeover or step switch function.
Three contacts for switching a three-stage fan.
Two contacts for activating the heating and cooling valves.
Supports 24V and 230V valves.
With two binary inputs for connecting dewpoint and condensation contacts.
The scanning voltage is provided by the device.
The bus connection is provided via the enclosed bus terminal.
Bus voltage: 24 V
Inputs: 2
Polling voltage: 10 V-
Outputs: 3 Normally open contact, potential free
Suitable for: AC3
Rated current: 6 A
Output voltage: 230 V~
Protection class (Device): IP 20
Temperature range (Device): -5 °C to 45 °C
Dimensions: (L x W x D): 90 mm x 108 mm x 64.5 mm
Module width: 6 MW
Bbn Order details Price Weight Pack
4016779 1 piece 1 piece unit
EAN Type code Order code kg pc.
180433 FCA-M-2.3.1 2CDG510010R0011 1
Blind Actuator, 4-fold, 230 V, MDRC
For controlling 4 independent blind or roller shutter drives.
The outputs are inversely blocked.
The bus can be connected via enclosed terminal block.
Bus voltage: 24 V 15
Outputs: 4
Suitable for: AC3
Rated current: 6 A, cos φ 0.45
Output voltage: 230 V~
Protection class (Device): IP 20
Temperature range (Device): -5 °C to 45 °C
Dimensions: (L x W x D): 90 mm x 72 mm x 64 mm
Module width: 4 MW
Bbn Order details Price Weight Pack
4016779 1 piece 1 piece unit
EAN Type code Order code kg pc.
941785 BA-M-0.4.1 2CDG510011R0011 1