Page 37 - IDEC timer catalogue
P. 37

Timers                                                                            GT3F Series


                                                       Part Numbering List

        GT3F
            Mode of      Rated     Time Range      Output          Contact    Optional Input   Complete Part Number
           Operation   Voltage Code                                                           8-Pin        11-Pin      Switches & Pilot Lights

                     AF20: 100 to            250V AC, 5A,      Delayed SPDT  Reset           GT3F-1AF20   GT3F-1EAF20
                     240VAC (50/60Hz)  0.1 seconds to   30V DC, 5A (resistive load)         GT3F-1AD24   GT3F-1EAD24
         Power OFF-delay
                                  600 seconds  250V AC, 3A,                  None (8p)       GT3F-2AF20   GT3F-2EAF20
                     AD24: 24V AC/DC                           Delayed DPDT
                                             30V DC, 3A (resistive load)     Reset (11p)    GT3F-2AD24   GT3F-2EAD24
              Optional reset input resets the contact to the OFF state before time out.


                                               Timing Diagrams/Schematics

        GT3F-1 Timing Diagrams                                                                                         Display Lights
                                   GT3F-1 (8-pin)                                       GT3F-1E (11-pin)
                                                  Delayed SPDT Output, with Reset Input
















          Item  Terminal Number                 Operation                                                              Relays & Sockets
                  2 - 7 (8p)
         Power
                 2 - 10 (11p)
         Reset   1 - 4 (8p)  ON or L
         Input  6 - 7 (11p)
                5 - 8 (8p)  (NC)
         Delayed   1 - 4 (11p)
         Contact  6 - 8 (8p)
                1 - 3 (11p)  (NO)                                                                                      Timers
         Indicator  POWER
         Set Time
                               Tr   T            Ta                Ts  T

             T = Set time            1.  For time ranges, see page 829.
             Ta = Shorter than set time  2.  For sockets and accessory part numbers, see page 838.
             Ts = 1 Second           3.  When power is applied, the NO output contact closes. When power is removed, the timing period
             Tr = Minimum Power Application Time  begins. When time has elapsed, the NO contact opens.
             GT3F-1: 1 Second        4.  For the timing diagram overview, see page 794.                                Terminal Blocks


























                                            USA: 800-262-IDEC          Canada: 888-317-IDEC                        827  Circuit Breakers