Page 29 - OTDC Switch
P. 29

OTDC S-SERIES                                                                      29




         —
         Technical data
         OTDC S2.0-Series IEC












          —
          Technical data according to IEC 60947 for switch-disconnectors OTDC100G_…250G_
          Switch size                                                     A   OTDC100G_ OTDC160G_ OTDC200G_ OTDC250G_
          Rated insulation voltage Ui  Pollution degree 2                 V   1500    1500     1500    1500            04
          Rated impulse withstand voltage                                 kV  12      12       12      12
          Rated thermal current Ith  1)  In open air, normal conditions  ) 2  A  100  160      200     250
                                    In enclosure 40°C                     A   100     160      200     250
                                    In enclosure 50°C                     A   100     160      200     250
                                    In enclosure 60°C                     A   100     160      200     219
                                    In enclosure 70°C                     A   100     146      169     185
                                    In enclosure 80°C                     A   88      115      133     146
          ...with cable or bar cross section  Cu                          mm² 35      70       95      120
          Rated operational   DC-21B  1000V      1 circuit   2P (1P+, 1P-)  A  100    160      200     250
          current Ie  ,                          2 circuits  4P (2P+, 2P-)  A  100    160      200     250
                3)
          poles in series
                                    1500V        1 circuit   2P (1P+, 1P-)  A  100    160      200     250
                                                 2 circuits  4P (2P+, 2P-)  A  100    160      200     250
                         DC-PV1     1000V        1 circuit   2P (1P+, 1P-)  A  100    160      200     200
                                                 2 circuits  4P (2P+, 2P-)  A  100    160      200     200
                                    1500V        1 circuit   2P (1P+, 1P-)  A  100    160      200     200
                                                 2 circuits  4P (2P+, 2P-)  A  100    160      200     200
                         DC-PV2     1000V        1 circuit   2P (1P+, 1P-)  A  100    160      200     200
                                                 2 circuits  4P (2P+, 2P-)  A  100    160      200     200
                                    1500V        1 circuit   2P (1P+, 1P-)  A  100    100      100     100
                                                 2 circuits  4P (2P+, 2P-)  A  100    100      100     100
          Rated short-time withstand current,   R.M.S. -value Icw         kA  10      10       10      10
          1500V, 0,1
          Rated short circuit making capacity,   Peak value Icm           kA  10      10       10      10
          1500V
          Power loss / pole         At rated current                      W   1,0...1,3  3,1...3,5  5,0...5,5  7,7...8,4
          Terminal bolt size        Metric thread diameter x length       mm  M8x25   M8x25    M8x25   M8x25
          Terminal tightening torque  Counter torque required             Nm  15…22   15…22    15…22   15…22
          Mechanical Endurance      Cycles                                -   10.000
          Operating altitude without derating                             m   ≤2000
          Operating torque          2P/4P                                 Nm  6…9     6…9      6…9     6…9
          1)  For more detailed derating, please consult us. Installation condition may have an influence on the derating by increasing the possible rated
          current. The given deratings are references based on specific test setup.
          2)  Normal conditions defined in IEC 60947-1, section 6.1.
          3)  For DC-22B utilization category ratings, please consult us.











         —
         OTDC100...250_G_