32               SWITCH-DISCONNECTORS OTDC AND OTDCP




         —
         Technical data
         OTDC S2.0-Series for higher short-circuit currents IEC and UL












          —
          Technical data in accordance to UL98B for photovoltaic disconnect switches OTDC100UG_…250UG_-ESS
          Suitable for use in photovoltaic systems in accordance with article 690 of the NEC.
          Switch size                                            OTDC100UG_-ESS   OTDC200UG_-ESS  OTDC250UG_-ESS
          UL Listed         Standard                             UL98B            UL98B          UL98B
          Rated ambient                                      °C  -20…+50          -20…+50        -20…+50
          temperature
          Rated current  1)  1000V      1 circuit  2P (1P+, 1P-)  A  100          200            250
                                        2 circuits  4P (2P+, 2P-)  A  100         200            250
                            1500V       1 circuit  2P (1P+, 1P-)  A  100          200            250
                                        2 circuits  4P (2P+, 2P-)  A  100         200            250
          Short circuit rating  1500V            R.M.S. -value  kA  10            10             10
          Required protection  2)                                Any              Any            Any
          Short circuit rating  1500V DC                     kA  50               50             50
          Required protection  3)  Max. fuse size            A   100              200            250
          Mechanical lug                                         OZXA 100         OZXA 200       OZXA 252
          Wire range                                             AWG 14-2/0       AWG 4-300MCM   2 X AWG 14-2/0
          Tightening torque                                  lb-in. 35-50         200            120
          Technical data according   See IEC table for type      OTDC160G_        OTDC250G_      OTDC250G_
          to IEC 60947
          1)  For more detailed derating please consult us. Installation condition may influence on the derating. The given deratings are references based on specific test setup.
          2)  Any suitable PV fuse or PV circuit breaker.
          3) Please consult us on the fuse coordination table for more information













          —