Page 30 - OTDC Switch
P. 30

30               SWITCH-DISCONNECTORS OTDC AND OTDCP




         —
         Technical data
         OTDC S2.0-Series IEC and UL












          —
          Technical data in accordance to UL98B for photovoltaic disconnect switches OTDC100UG_…250UG_
          Suitable for use in photovoltaic systems in accordance with article 690 of the NEC.
          Switch size                                                        OTDC100UG_  OTDC200UG_   OTDC250UG_
          UL Listed                     Standard                             UL98B       UL98B        UL98B
          Rated ambient temperature without                            °C    -20…+50     -20…+50      -20…+50
          derating
          Rated current                 1000V      1 circuit  2P (1P+,1P-)  A  100       200          250
                                                   2 circuits  4P (2P+,2P-)  A  100      200          250
                                        1500V      1 circuit  2P (1P+,1P-)  A  100       200          250
                                                   2 circuits  4P (2P+,2P-)  A  100      200          250
          Short circuit rating          1500V                          kA    10          10           10
          Required protection  2)                                            Any         Any          Any
          Mechanical lug                                                     OZXA 100    OZXA 200     OZXA 252
          Wire range                                                         AWG 14-2/0  AWG 4-300MCM  2 X AWG
                                                                                                      14-2/0
          Tightening torque                                            lb-in.  35-50     200          120
          Technical data according to IEC 60947  See IEC table for type      OTDC160G_   OTDC250G_    OTDC250G_
          1)  For more detailed derating please consult us. Installation condition may have an influence on the derating. The given deratings are references
          based on specific test setup.
          2)  Any suitable PV fuse or PV circuit breaker.










          —
          OTDC100...250_G_