Page 60 - Sace Emax 2 Catalogue
P. 60

3/36             SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —     Extremely Inverse
          t
                Very Inverse
                Standard Inverse  8
          Description of protection functions


                       I

          t

                   U8
                            UV
              t8
                       V   In addition to the protection functions, the following indication and control functions are available to
                           warn the user that a given condition has been reached. The active indications are always shown on the
          t                display and are also available by communication on the system bus (with Ekip Com modules) or electri-
                           cal indication (with Ekip Signalling modules).
                  U9
                            OV
                    t8 t9  Synchrocheck (SC - ANSI 25): the synchronism control function compares the voltages in the modules
                       V   as well as the frequencies and phases of two circuit breakers to which the circuit breaker is connected.
                           Ekip Touch indicates that conditions have been reached that enable the two lines to be made parallel.
          t                The function is available with two work modes:
                           •  In systems with both busbars supplied, where synchronism is determined by:
               U, f,
                            UF
                   f12      1.  voltage of the two half-busbars above the Ulive threshold for the set time
                            2.  difference of the module of the two voltages below the threshold ΔU
             t12            3.  difference in the frequency of the two voltages below the threshold Δf
             t12
                       f    4. difference in the phase of the two voltages below the threshold Δ
                            5.  desirable time for synchronism condition tsyn
          t                 6. circuit breaker open
                           •  In systems with an out-of-service line (dead busbar), where the synchronism condition is determined
                            OF
                            by the concurrence of the following conditions for the tref set time:
                  f13
                            1.  voltage of the active half-busbar above threshold Ulive
                   t13      2.  voltage of the dead half-busbar below   threshold Udead
                       f    3.  circuit breaker open
                           In both cases, synchronism consent is withdrawn when one of the above conditions is missing and it
                           has not been less than 200ms from the change of the circuit- breaker condition (when the relationship
                    mean
                           has been set).
                            voltage unbalance
                     U14   The indication of reached synchronism is available directly as an electrical indication via a contact that
                           is always supplied with the module. The function can be activated simply by connecting the Ekip Syn-
                           chrocheck module.
            U1  U2  U3

                           Cyclical direction of the phases (ANSI 47): indicates an alarm through inversion of the phases sequence.
                V1
                            senso ciclico


            V3      V2



                           Power factor (ANSI 78): available with a three-phase threshold, warns when the system operates with a
                           power factor that is less than the set power factor.


                           The following protections are also available:
                           Second time-delayed overcurrent protection (S2 – ANSI 50TD): in addition to the standard protection
                           S, a second (excludable ) time-constant protection is available that enables two independent thresh-
                           olds to be set in order to ensure precise selectivity, especially in highly critical conditions.
   55   56   57   58   59   60   61   62   63   64   65