3/40             SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          Description of protection functions













                           Rate of change of frequency (ROCOF – ANSI 81R): enables both positive and negative frequency varia-
          f(Hz)   frequency
                  after failure  tions to be rapidly detected . The protection is constant and is tripped when the frequency variation in
            failure
                           Hz/s is greater than the set threshold.
            50/60Hz
                  frequency
                  after failure
                   Time


                           Second protection against voltage controlled overcurrent protection (S2(V) - ANSI 51V): available in
          t     1
               Ks          addition to the protection S(V), enables total selectivity to be achieved in all installations.
          t21
                 Ks
          t20
                       I
            KsxI20  I20  I21
              KsxI21

                           Second protection against loss of field or reverse reactive power (RQ – ANSI 40 or 32R): enables the
          Q
                           generator’s de-energization curve to be followed very accurately, thereby avoiding any unnecessary dis-
                  kq  kq2
                           connection.
                      P
          Q25
          Q24