Page 55 - Sace Emax 2 Catalogue
P. 55

PROTECTION TRIP UNITS                                                            3/31



















                                                                                                                       03







 Record of values: of the parameter for each interval with time-stamping   Parameters  Window  Intervals  Ekip Touch  Ekip Hi-Touch  Ekip G Touch  Ekip G Hi-Touch
 Current: minimum and maximum  [A]  I Min, I Max  Fixed  synchronizable by   Duration: 5…120min
          remote               Number of intervals: 24
 Phase-phase voltage: minimum and maximum  [V]  U Min, U max
 Active power: average and maximum  [kW]  P Avg, P Max
 Reactive power: average and maximum  [kVAR]  Q Avg, Q Max
 Apparent power: average and maximum  [KVA]  S Avg, S Max

 Data logger: record of high sampling rate parameters   Parameters
 Currents  [A]  L1, L2, L3, Ne, Ig
 Voltages  [V]  U12, U23, U31
 Sampling rate  [Hz]  1200-2400-4800-9600
 Maximum recording duration  [s]  13.6
 Recording stop delay  [s]  0-10s
 Number of registers  [no]  2 independent

 Information on trip and opening data: after a fault without auxiliary supply  Parameters
 Type of protection tripped  eg. L, S, I, G, UV, OV
 Fault values per phase  [A/V/Hz W/var]  eg. I1, I2, I3, neutral for S protection
 V12, V23, V32 for UV protection
 Time-stamping  Date, time and progressive number

 Maintenance indicators  Parameters
 Information on last 30 trips  Type of protection, fault values and time-stamping
 Information on last 200 events  Type of event, time-stamping
 Number of mechanical operations  (1)  [no]  Can be associated to alarm
 Total number of trips  [no]
 Total operating time  [h]
 Wear of contacts  [%]  Prealarm >80%
 Alarm = 100%
 Date of maintenance operations performed  Last
 Indication of maintenance operation needed
 Circuit-breaker I.D.  Type of circuit breaker, assigned device name, serial number

 Self-diagnosis  Parameters
 Check of continuity of internal connections  Alarm due to disconnection: rating plug, sensors, trip coil      Note: Opening of circuit
 Failure of circuit breaker to open (ANSI 50BF)  Alarm following non-tripping of protection functions  breaker can be set in the
          event of alarm
 Temperature (OT)  Prealarm and alarm for abnormal temperature
 (1) with auxiliary supply present
 Note: In case of Black trip units, 0.4% In is the lowest current value detected by Emax 2




          Key:
          -    not available
              available
              available with the dedicated software package