Page 70 - Sace Emax 2 Catalogue
P. 70

4/6              SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



               —

               Load Shedding








               Emax 2 has built-in load shedding algorithms to avoid power
               unbalance in the low voltage plant and stress for all the components.

                           Purpose                                     All the versions are available on Emax 2 platform for
                           ABB Emax 2 embeds patented functions based on   both the Microgrid situations, sharing some infor-
                           load shedding which reduces the Microgrid stress   mation about the loads under control in the plant.
                           in all situations. Typically it is the main protection
                           relay of the low voltage Microgrid located at the   Application examples
                           interface point with the medium voltage grid,   •  Grid-connected plants with running GenSets,
                           able to control the plant in every circumstances.  which contribute to the self-consumption to-
                                                                        gether with potential renewable sources and
                           Microgrid in islanding operation             support the load power supply in emergency
                           After the Emax 2 circuit breaker opens, because   conditions. It is the case of hybrid PV-diesel re-
                           of interface protection systems intervention or   mote communities connected to weak distribu-
                           external command, the Microgrid should transit   tion-grids where there are a lot of daily faults,
                           from on-grid to off-grid state with bumpless   or of facilities located in geographical areas
                           transition. When it is standalone, the power ab-  where there are frequent environmental events,
                           sorption from the main grid ceases, so that the   for example hurricanes or earthquakes.
                           Microgrid loads remains supplied by the local   •  Grid-connected plants with back-up GenSets
                           generation, like diesel GenSet or energy storage   started up after main - gen transfer switching
                           systems. This Microgrid generation can be always   logics that require high reliability. For example,
                           active or started up by an automatic transfer   hospitals, banks or data centers.
                           switching (ATS) logic after the disconnection
                           from the main grid, depending on the plant con-  Benefits
                           figuration. During the islanding transition, it is   Thanks to Emax 2 with embedded Load Shedding
                           very important to avoid the frequency drop, oth-  innovation, the following benefits are guaranteed:
                           erwise the generation protections could trip   Service continuity
                           jeopardizing the Microgrid stability with conse-  •  When a plant remain disconnected from the main
                           quently a long downtime. Emax 2, employing the   grid, even if local production is present, there is
                           current and voltage measurements, integrates   a significant stress that turns off all the genera-
                           two different fast load shedding logics to reduce   tors with consequent blackout. Load Shedding
                           this blackout risk, protecting the Microgrid   logics embedded in Emax 2 reduce the frequency
                           during the intentional or unintentional islanding   drop that usually makes the local generation pro-
                           operation:                                   tection trip, maintaining the plant live.

                           •  Basic Load Shedding, simple logic able to rec-
                            ognize the Microgrid disconnection event and
                            shed a group of not priority loads thus ensuring
                            a fast time response and power balance.
                           •  Adaptive Load Shedding, the advanced algo-
                            rithm available with Emax 2 as an enhancement
                            of the basic version. The intelligent software
                            embedded in the unit sheds very quickly the not
                            priority loads according to the Microgrid power
                            consumption and frequency measurements.
                            Moreover, such software has a dedicated con-
                            figuration for backup generation related to ATS
                            and the software itself is even able to estimate
                            the energy produced by a solar plant based on
                            plant geography settings.
   65   66   67   68   69   70   71   72   73   74   75