ABB | SACE Emax 2
       3 - Class 1 Power & Energy Metering



                List and performance Presence of the Class 1 Power & Energy Metering package allows higher measuring accuracy to be obtained
                                    for the following quantities:
                                                                                                      Accuracy of
                                     Measurement           Monitor time (min-max)  Normal operating range
                                                                                                      read value
                                                                                Standard IEC61557-12,
                                     Phase currents  (6)(8)  0,004 ÷ 64 In                            0,5 %   (1)
                                                                                tables 20-22
                                                                                Standard IEC61557-12,
                                     Internal earth fault current  (2)  0,08 ÷ 64 In                  0,5 %   (1)
                                                                                table 20
                                     Line frequency       30 ÷ 80 Hz   (3)      fn ± 10 %   (4)       ± 0,02 Hz
                                     Total active and apparent   |Pmin ÷ Pmax|  (5)  Standard IEC61557-12,   1 %   (1)
                                     power  (7)                                 tables 8-11-14
                                     Active and apparent phase        (5)       Standard IEC61557-12,      (1)
                                     power                |Pmin ÷ Pmax|         tables 8-11-14        1 %
                                     Total active and apparent   1 kWh ÷ 2 TWh; 1 kVARh ÷  Standard IEC61557-12,   1 %  (1)
                                     energy               2 TVARh; 1 kVAh ÷ 2 TVAh  tables 8-11-14
                                                                                Standard IEC61557-12,
                                     Power factor         0,5 ÷ 1                                     1%   (1)
                                                                                table 27

                                    (1)  the accuracy values refer to the normal operating intervals and conditions established by IEC 61557-12, for
                                    each quantity and class declared
                                    (2)  available with LSIG versions
                                    (3)  available for voltage values of over 30 V (with Un < 277 V) or 60 V (with Un ≥ 277 V)
                                    (4)  47 ÷ 55 Hz with fn = 50 Hz; 54 ÷ 66 Hz with fn = 60 Hz
                                    (5)  Pmin = 0,5 In x 5 V; Pmax= 3 x 16 In x 900 V
                                    (6)  the higher phase currents are also available in the Histograms, Measuring instruments and Measurement
                                    summary pages
                                    (7)  the higher total powers are also available in the Measuring instruments and Measurement summary pages
                                    (8)  internal phase current; in the presence of an external Neutral, the accuracy of current Ne is 1%


            Functional characteristics The measuring performance of the Class 1 Power & Energy Metering package is guaranteed in the following
                                    conditions (from table 43 of standard IEC61557-12):
                                     Characteristic                     Value
                                     Classification of performance measuring and
                                     monitoring device (PMD) in accordance with   PMD-DD
                                     chapter 4.3 of the standard
                                                                        Operating: T= -25°C to +70°C; Storage: T = -30°C to
                                     Temperature
                                                                        +70°C; Class: K70
                                                                        Up to 90% relative humidity without condensation; From
                                     humidity and altitude
                                                                        0 to 2000 meters
                                     Performance class for active energy and power 1




                   Information page Presence of the Class 1 Power & Energy Metering package activates the IEC61557 12 information page,
                                    which can be consulted in the About menu













                                    Figure 28

                                    The page shows the activation state of the Class 1 Power & Energy Metering package (Activated/Deactivated)
                                    and the serial numbers of certain accessories installed on the CB for the specific purpose of conforming to
                                    the characteristics of the package (electronic units and internal current sensors)


       117 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A           Ekip Touch - Measurements | 3 - Class 1 Power & Energy Metering