Page 120 - Sace Emax 2 Manual for design engineers
P. 120

ABB | SACE Emax 2
       4 - Datalogger



                       Presentation The datalogger is a function which allows data associated with a trigger event to be recorded. The following
                                    data are recorded:
                                     •  Analog measurements: line-to-line voltages and phase currents
                                     •  Digital events: protection events or alarms, circuit-breaker status signals, protection trips.
                                    One or two independent recordings can be configured and, via Ekip Connect, all the associated information
                        Datalogger  can be downloaded, displayed and saved.

                           Function When the datalogger is enabled and activated (RESTART), Ekip Touch continuously acquires data by filling
                                    and emptying an internal buffer (B).
                                    If a trigger event (A) occurs, Ekip Touch interrupts acquisition (STOP) immediately or after a time that can
                                    be set by the user (C) and stores all the data of the window (D), which can then be downloaded to a PC for
                                    reading and analysis.
                                           IMPORTANT: the function requires an auxiliary voltage supply



















                                    Figure 29



                       Parameters 1 The parameters and commands of the function are available in the Settings menu (page 46).
                                     Parameter    Description                                           Default
                                                  Activates/deactivates the function and its availability in the parameters
                                                  menu
                                     Enable                                                             Off
                                                       NOTE: il the enable command is hidden when at least one
                                                     datalogger is activated
                                                  Determines the number of recordings (1 or 2)
                                     Num. of
                                     Datalogger        NOTE: the recordings share the settings of the sampling frequency  1
                                                     and type of memory
                                                  Establishes the number of samples acquired per second and the
                                                  recording window.
                                                  Four options are available: 1200 Hz (window= 13.6 s), 2400 Hz (6.8 s),
                                     Sampling     4800 Hz (3.4 s), 9600 Hz (1.7 s)                      9600 Hz
                                     frequency         NOTE:
                                                      • A high frequency allows the data to be analyzed more accurately
                                                      • if there are two dataloggers, the recording window of each
                                                     recording is halved
                                     Datalogger 1   Menu with the parameters of each Datalogger: trigger event, recording
                                     and 2        delay and Restart/Stop commands
                                     Restart and   Synchronized start and stop commands of the two dataloggers, valid and
                                     Stop Both    available with Num. of Datalogger = 2













       118 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                        Ekip Touch - Measurements | 4 - Datalogger