Page 124 - Sace Emax 2 Manual for design engineers
P. 124

ABB | SACE Emax 2
              Counters - introduction The main counters of the function are available in the Measurements – Network Analyzer menu, distributed
                                    among several sections (page 45).
                                    The extended list of all the measurements is available via Ekip Connect or by connecting to the bus system

                                           NOTE: the Additional List item in the following paragraphs contains the additional counters
                                               that are only present via Ekip Connect; the type of reference counter is given in the
                                           heading of the additional tables


               V Sequences and V 3s  Submenus V Sequences and V 3s Sequences have the following counters:
                         Sequences
                                     Menu         Parameter    Description
                                                  V seq pos    Positive sequence of period in progress [V]
                                                  V seq neg    Negative sequence of period in progress [V]
                                     V Sequences
                                                  Last V pos seq  Positive sequence of period preceding the one in progress [V]
                                                  Last V neg seq  Negative sequence of period preceding the one in progress [V]
                                                  V seq pos    Positive sequence calculated during the last three seconds [V]
                                     V 3s Sequence  V seq neg  Negative sequence calculated during the last three seconds [V]
                                                  Unbalance    Voltage unbalance calculated during the last three seconds [%]

                                    Additional List
                                     Counters (Sequences)      Description
                                     Last time stamp           Date and time of last recording of the sequences
                                     Counters (Sequences)      Description
                                     Last value                Voltage unbalance relating to the period in progress [%]
                                                               Voltage unbalance relating to the period preceding the one in progress
                                     Actual unbalance value
                                                               [%]
                                     Last time stamp           Date and time of last recording of the unbalances
                                                               Counts the number of times that the average value of the ratio
                                                               between the positive on negative sequence (with direction of rotation
                                     Actual number of U.
                                                               3-2-1) and negative on positive sequence (1-2-3) exceeds the
                                                               Unbalance V Th threshold; the count refers to the actual day
                                     Actual [day -1 ... day -7]    Counters relating to the number of unbalances detected in the last
                                     number of U.              seven days of activity, calculated using the internal clock of the unit
                                                               Cumulative counter of all the unbalances detected by the unit (sum of
                                     Cumulative number of U.
                                                               the other counters or to be increased also for the previous days?)

                                           NOTE: all measurements of unbalances (Not balanced and Unbalance value) saturate at
                                               200%



       THD Current and THD Voltages The THD Current and THD Voltages submenus have the following counters:
                                     Menu         Counters     Description
                                     THD Current  L1, L2, L3, Ne  Instantaneous harmonic distortion value of each current phase
                                     THD Voltages  U12, U23, U31  Instantaneous harmonic distortion value of each line-to-line voltage






















       122 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                    Ekip Touch - Measurements | 5 - Network Analyzer
   119   120   121   122   123   124   125   126   127   128   129