ABB | SACE Emax 2
       5 - Network Analyzer



                       Presentation The Network Analyzer function allows you to set voltage and current controls over a long period, in order to
                                    analyze your system.
                                    To this purpose, voltages and currents are monitored, so as to find:
                                     •  voltage sequences (Over, Under, Pos and neg)
                                     •  unbalance between voltages (Unbalance)
                                     •  short voltage drops (Interruption) and slow sags (Sag)
                                     •  short voltage increases (Spikes) and slow swells (Swell)
                                     •  harmonic distortion of voltages and currents (THD)
                                    Each monitoring is associated with control parameters set by the user and updated each time the set control
                                    conditions occur.


                        Parameters The configuration parameters of the counters are available in the Settings - Network Analyzer menu (page 46).
                                    The Monitor time parameter, which defines the length of each monitoring session, can also be set in the
                                    Settings menu.
                                           NOTE: the parameter is the one used for measuring the maximum currents and voltages
                                    Main Menu
                                     Parameter     Description                                         Default
                                                   Activates/deactivates the function and its availability in the parameters
                                     Enable                                                            Off
                                                   menu
                                     I Harmonic
                                     Analysis      Activates harmonic analysis of the currents         Off
                                     V Harmonic    Activates harmonic analysis of the voltages         Off
                                     Analysis
                                                   Control threshold of the Under V Th counter
                                     V Threshold Low  The value is given as a percentage of rated voltage Un and can be set  85 % Un
                                                   within the range: 75% to 95%, in 5% steps.
                                                   Control threshold of the Over V Th counter
                                     V Threshold High  The value is given as a percentage of rated voltage Un and can be set  110 % Un
                                                   within the range: 105, 110, 115 % Un
                                                   Alarm threshold for the Unbalance counter.
                                                   The value is given as a percentage of rated voltage Un and can be set
                                     Unbalance V Th  within the range: 2% to 10% Un, in 1% steps.      3 % Un
                                                       NOTE: 0% =symmetrical and balanced system

                                                   Control threshold of the V microinterr counter.
                                     V microinterr. Th  The value is given as a percentage of rated voltage Un and can be set  95 % Un
                                                   within the range: 10% to 95% Un, in 5% steps
                                                   Control threshold of the Spike counter.
                                     V Spike Threshold The value is given as a percentage of Un and can be set within the   105 % Un
                                                   range: 105% to 125% Un, in 5% steps
                                     Sags          Menu with the control parameters of the voltage sags
                                     Swells        Menu with the control parameters of the voltage swells
                                                   The submenu, which becomes available by enabling the harmonic
                                     Harmonics     current and/or voltage analysis, allows the harmonic control
                                                   parameters to be configured



                                                                                                  Continued on the next page