           THD Voltages and Currents Certain  counters  relating  to  harmonic  distortion  are  available  in  the  Counters  -  Day  -1  and  Counters  -
                                    Cumulative submenus:
                                     Counters (Swells Long)    Description
                                                               Counts the total number of minutes in which total distortion exceeds
                                     THD Voltages
                                                               current threshold THD Threshold
                                                               Counts the total number of minutes in which total distortion exceeds
                                     THD Current
                                                               voltage threshold THD Threshold

                                           NOTE: the counters saturate at 65535 minutes (45 days); they can be reset by a service
                                               connector command (via Ekip Connect) or via communication from the system bus
                                    Additional List

                                     Counters (Swells Long)    Description
                                     Actual minutes            THD Current count for the current day [min]
                                     Actual [day -2 ... day -7]    THD Current count of the last seven days of activity, calculated using
                                     number of THD C.          the internal clock of the unit

                                     Counters (Swells Long)    Description
                                     Actual minutes            THD Voltages count for the current day [min]
                                     Actual [day -2 ... day -7]    THD Voltages count of the last seven days of activity, calculated using
                                     number of THD C.          the internal clock of the unit




                         Waveforms The Network Analyzer - Waveforms menu provides graphic representations of:
                                     •  phase currents L1, L2, L3, Ne (for units configured with 4 phases)
                                     •  line-to-line voltages V12, V23, V31
                                    When one of the available quantities is selected, Ekip Touch acquires and displays the waveform













                                    Figure 30

                                    The detected waveform and the value at the time of selection are displayed in the window that appears. A
                                    new waveform and the relative measurement can be acquired with the Refresh command (1).
                                    Harmonics
                                    The waveform window will propose the  Harmonics (2) command if harmonic analysis of currents and/or
                                    voltages has been selected. This command accesses the histogram of the harmonics (relating to the grid
                                    frequency set in the menu) that make up the waveform.














                                    Figure 31
                                    Touch the sides of the display to scroll the harmonics after (3) and before (4) the selected harmonic, displayed
                                    on a flashing graph with value shown in the center of the page. The command for exiting the page is at the
                                    top left (5).