Page 193 - Sace Emax 2 Manual for design engineers
P. 193

ABB | SACE Emax 2
       2 - Ekip Com Modbus RTU



                                    Ekip Com Modbus RTU is a communication accessory which allows Ekip Touch to be integrated into an RS-
                                    485 network with Modbus RTU communication protocol, remote supervision and monitoring functions, in two
                                    different modes, master and slave.
                                    You can perform the following operations remotely:
                                     •  read Ekip Touch measurements and information
                                     •  manage certain controls, including opening and closing the actuator
                                     •  access information and parameters not available on the display
                                     •  If connected to a withdrawable version of the circuit-breaker, the allows the racked-in/racked-out status
                                       to be detected
                                           NOTE: the remote open and close commands of the circuit-breaker can only be executed if
                                               Ekip Touch is in the Remote configuration and the circuit-breaker is equipped with the
                                           Ekip Com Actuator module (page 234)
                                    Ekip Com Modbus RTU is always supplied with contacts Ekip AUP and Ekip RTC (page 234.
                                    The System Interface document is available for mapping the module in its communication network. All the
                                    required communication and command details are listed in the document (page 182).



                            Models Two different modules compatible with the Modbus RTU protocol are available: Ekip Com Modbus RTU and
                                    Ekip Com Modbus RTU Redundant.
                                    The modules are identical in terms of characteristics and installation methods, except for: display menus,
                                    cabling and addresses for system communication, which are specific for each module.
                                           NOTE: if different indications are not given, the information in the next chapter is valid for
                                               both models
                                    The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the unit
                                    (e.g. for applications where high grid reliability is required).
                                           IMPORTANT: each Ekip Touch can be fitted with only one module per type. The
                                               configuration with two modules of the same model is not allowed (example: two
                                           Ekip Com Modbus RTU Redundant)



                       Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply, either on the
                                    circuit-breaker (fixed version) or on the fixed part (withdrawable version).
                                    To connect the module to its communication network and for references about the terminals, please consult
                                    document 1SDM000091r0001; use Belden 3105A type cables or equivalent for the external cabling.
                                    To connect the module to Ekip Touch, please consult document 1SDH001000r0512.


                       Power supply Ekip Com Modbus RTU is supplied directly by the Ekip Supply module to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence of
                                               auxiliary power supply

























       191 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A               External electronic accessories | 2 - Ekip Com Modbus RTU