                           Interface the module has three signaling leds:














                                    Figure 123
                                     LEDs     Description
                                              Signals the on status and correct communication with Ekip Touch:
                                               • off: module off
                                               • on steady or flashing synchronized with the Power led of Ekip Touch: module on and
                                     Power
                                              communication with Trip unit present.
                                               • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per second):
                                              module on and communication with Trip unit absent.
                                              Indicates the status of the communication between network master and module (slave):
                                     Rx        • off: Modbus RTU communication not activated
                                               • on with fast flashes: Modbus RTU communication activated
                                              Indicates the status of the communication between network master and module (slave):
                                     Tx        • off: communication between Modbus RTU not activated
                                               • on with fast flashes: Modbus RTU communication activated



                      Configurations

                                                                                                     ON




                                                                                                    1  2  3  4



                                    Figure 124

                                     Resistor   Dip       Description                                    Default
                                                         120 Ω termination resistor
                                     Rterm      1 and 2                                                  Off
                                                         Move dip-switches 1 and 2 to the ON position to connect Rterm
                                                         220 Ω pull-up or pull-down resistor
                                     Rpol       3 and 4                                                  Off
                                                         Move dip-switches 3 and 4 to the ON position to connect Rpol

                                           IMPORTANT: move the dip-switches before connecting the module to Ekip Supply
                                               and the communication network