Page 205 - Sace Emax 2 Manual for design engineers
P. 205
ABB | SACE Emax 2
6 - Ekip Com Profinet
Ekip Com Profinet is a communication accessory which allows Ekip Touch to be integrated into an Ethernet
network with Profinet communication protocol, with remote supervision and monitoring functions.
The module is configured as master and remotely, you can:
• read Ekip Touch measurements and information
• manage certain controls, including opening and closing the actuator
• access information not available on the display
• If connected to a withdrawable version of the circuit-breaker, the allows the racked-in/racked-out status
to be detected
NOTE: the remote open and close commands of the circuit-breaker can only be executed if
Ekip Touch is in the Remote configuration and the circuit-breaker is equipped with the
Ekip Com Actuator module (page 234)
Ekip Com Profinet is always supplied with contacts Ekip AUP and Ekip RTC (page 234).
The System Interface document is available for mapping the module in its communication network. All the
required communication and command details are listed in the document (page 182.
The ports used by the module are:
Ethertype Port Service Notes
0x88CC - LLDP Link Layer Discovery Protocol
0x8892 (Profinet) - Profinet IO Specific for real time communications (RT)
Profinet-cm
0x0802 34964/udp DCE/RPC
(Context manager)
Safety and cyber security Since the module allows the actuator connected to Ekip Touch and access to the data in the unit to be
checked, it can only be connected to networks equipped with all the necessary security and prevention
measures against unauthorized access (for example, the network of the control system of an installation).
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between the module and customer network or any other network (as the
case may be). The plant manager must establish and maintain appropriate measures
(such as but not limited to the installation of firewalls, application of authentication
measures, encryption of data, installation of antivirus programs, etc.) to protect the
product, the network, the customer system and interface against any kind of security
breaches, unauthorized access, interference, intrusion, loss and/or theft of data or
information. ABB and its affiliates are not liable for damages and/or losses related to
such security breaches, unauthorized accesses, interference, intrusion, loss and/or
theft of data or information.
• The module cannot be connected directly to the Internet. Only connect to dedicated
Ethernet networks with Profinet communication protocol
Models Two different modules compatible with the Profinet protocol are available: Ekip Com Profinet and Ekip Com
Profinet Redundant.
The modules are identical in terms of characteristics and installation methods, except for: display menus,
cabling and addresses for system communication, which are specific for each module.
NOTE: if different indications are not given, the information in the next chapter is valid for
both models
The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the unit
(e.g. for applications where high grid reliability is required).
IMPORTANT: each Ekip Touch can be fitted with only one module per type. The
configuration with two modules of the same model is not allowed (example: two
Ekip Com Profinet Redundant)
203 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A External electronic accessories | 6 - Ekip Com Profinet