ABB | SACE Emax 2
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Parameter for changing the configuration of the module from Server
Only to Client and Server and for integrating it into an interactive data
Client/Server exchange network (see Ekip Com Hub on page 216) Server only
IMPORTANT: if Client/Server, the module allows data
exchange like a normal Server function
IEEE 1588 Allows the IEEE 1588 protocol for distribution of the clock and OFF
enable synchronization signal to be enabled .
(1)
Master IEEE Enables the module to be set up as a master in the the network OFF
1588 segment to which it belongs (synchronization clock).
IEEE 1588 delay Allows the data exchange mode between module and master, either
mechanism Peer-to-Peer or End-to-End, to be selected. End-to-End
SNTP Client Allows the SNTP protocol for distribution of the clock and OFF
enable synchronization signal to be enabled (1)
Force Static IP Allows the network server that supplies the SNTP to be set. 0.0.0.0
Address
Time zone Defines the time zone to be used for synchronism +00:00
Daylight Saving Used to select whether daylight saving time is present (ON) or not
Time (OFF) in the country to which the synchronization time refers OFF
Permits (Enabled ARP) the periodic generation of a Gratuituos ARP
Disabilita
Gratuitos ARP message, used by Ekip Connect to rapidly find the modules via ARP Enabled
Ethernet scan without knowing the IP address beforehand
Access
protected by Enables the writing operations performed via the network to be Standard mode
password protected by a password (Request password)
Password With access protected by enabled password, this is the password to Local access
Modbus TCP use before each writing session .
(2)
(1) Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2) the parameter can only be changed via system bus in the remote configuration
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
Boot and HW version General module information
Flash CRC status e result Information about the correctness of the SW in the module
Stato Ekip Link Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server State of synchronism with SNTP server
Synchronisation
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP Master
IEEE 1588 status
Active) or absence (PTP Master but Passive) of the higher level master
202 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A External electronic accessories | 5 - Ekip Com Modbus TCP