Page 204 - Sace Emax 2 Manual for design engineers
P. 204

ABB | SACE Emax 2
              Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Parameter    Description                                         Default
                                                  Parameter for changing the configuration of the module from Server
                                                  Only to Client and Server and for integrating it into an interactive data
                                     Client/Server  exchange network (see Ekip Com Hub on page 216)   Server only
                                                       IMPORTANT: if Client/Server, the module allows data
                                                     exchange like a normal Server function
                                     IEEE 1588    Allows the IEEE 1588 protocol for distribution of the clock and   OFF
                                     enable       synchronization signal to be enabled .
                                                                             (1)
                                     Master IEEE   Enables the module to be set up as a master in the the network   OFF
                                     1588         segment to which it belongs (synchronization clock).
                                     IEEE 1588 delay  Allows the data exchange mode between module and master, either
                                     mechanism    Peer-to-Peer or End-to-End, to be selected.         End-to-End
                                     SNTP Client   Allows the SNTP protocol for distribution of the clock and   OFF
                                     enable       synchronization signal to be enabled  (1)
                                     Force Static IP   Allows the network server that supplies the SNTP to be set.  0.0.0.0
                                     Address
                                     Time zone    Defines the time zone to be used for synchronism    +00:00
                                     Daylight Saving  Used to select whether daylight saving time is present (ON) or not
                                     Time         (OFF) in the country to which the synchronization time refers  OFF
                                                  Permits (Enabled ARP) the periodic generation of a Gratuituos ARP
                                     Disabilita
                                     Gratuitos ARP  message, used by Ekip Connect to rapidly find the modules via   ARP Enabled
                                                  Ethernet scan without knowing the IP address beforehand
                                     Access
                                     protected by   Enables the writing operations performed via the network to be   Standard mode
                                     password     protected by a password (Request password)
                                     Password     With access protected by enabled password, this is the password to   Local access
                                     Modbus TCP   use before each writing session .
                                                                          (2)
                                    (1)  Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
                                    (2)  the parameter can only be changed via system bus in the remote configuration


                 Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Information          Description
                                     Boot and HW version  General module information
                                     Flash CRC status e result  Information about the correctness of the SW in the module
                                     Stato Ekip Link      Signals Ethernet cable connection errors
                                     SNTP Server Error    Error in communication with SNTP server
                                     SNTP Server          State of synchronism with SNTP server
                                     Synchronisation
                                                          Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP Master
                                     IEEE 1588 status
                                                          Active) or absence (PTP Master but Passive) of the higher level master
























       202 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A               External electronic accessories | 5 - Ekip Com Modbus TCP