Page 233 - Sace Emax 2 Manual for design engineers
P. 233

ABB | SACE Emax 2
          Enabling and measurements The individual inputs of the modulecan be enabled in the Ekip Signalling 3T page: I42 Temperatures, I43
                                    Temperatures, I44 Temperatures, I41 Current 4-20mA (per 3T-1), I52 Temperatures, I53 Temperatures, I54
                                    temperatures, I51 Current 4-20mA (for 3T-2).
                                     Parameter          Description                                      Default
                                                        Enables the specific input and relative alarm state and signaling
                                     Enable                                                              Enabled
                                                        controls to be activated



                       Alarm signals Up to three alarm thresholds (independent of each other), Threshold A, Threshold B, Threshold C, can be
                                    activated and configured for each input in the Protection parameters - Other parameters A (and B if dual set
                                    is activated) page
                                    Each alarm threshold has the following configuration parameters:

                                           NOTE: the table lists the parameters of threshold A of input I42; the names and references
                                               of all the other thresholds and inputs change

                                     Parameter      Description                                        Default
                                     Threshold A enable Activates verification of input I42 with alarm Threshold A  Off
                                                    Defines whether the alarm must activate when measurement is
                                     Threshold A
                                     hysteresis direction  above (Up) or below (Down) the set value, with reference to the   Up
                                                    Threshold A setting
                                                    Alarm threshold A of input I42. The value is given in degrees Celsius
                                                    (°C) and can be set within the range: -40°C to 240°C, in 0.1°C
                                                    steps.                                             200 °C (I42,
                                                                                                       I43, I44, I52,
                                     Threshold A value   NOTE: the thresholds of the 4-20mA (I41 and I51) Current   I53, I54) / 50
                                                        Loop input are given in percentage form and can be set within   % (I41, I51)
                                                        the range: 0% to 100 %, in 0.1% steps (each step equivalent
                                                        to 0.016µA)
                                                    Hysteresis value, valid for quitting the alarm condition if the set
                                                    Treshold A alarm threshold has been exceeded.
                                                    The hysteresis parameter only allows positive values. The trip unit
                                                    decides whether to add or subtract this value to or from the alarm
                                                    threshold on the basis of the direction parameter, example:
                                                     • Direction = Up, Value = 200°C, hysteresis= 10°C, the alarm   1 °C (I42, I43,
                                     Threshold A    activates over 200° and de-activates below 190°C   I44, I52, I53,
                                     hysteresis                                                        I54) / 1 % (I41,
                                                    The value is expressed in degrees Celsius (°C) and can be set within   I51)
                                                    the range: 0°C to 50°C with 0.1°C steps.
                                                         NOTE: the thresholds associated with the 4-20mA (I41 and
                                                        I51) Current Loop input are given in percentage form and can
                                                        be set within the range 0% to 30 %, in 0.1% steps (each step
                                                        equivalent to 0.016µA)



                   States and alarms The state of all control thresholds can be checked in the Warnings/Alarms page





























       231 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                  External electronic accessories | 13 - Ekip Signalling 3T