Page 235 - Sace Emax 2 Manual for design engineers
P. 235

ABB | SACE Emax 2
       3 - Ekip Multimeter



                                    Ekip Multimeter is a remote display panel-front module with touchscreen display allowing the parameters of
                                    the Trip unit to which it is connected via local bus to be displayed and edited.
                                    Up to four Ekip Multimeter modules can be connected to the same Trip unit. On the other hand, the module
                                    can only be connected to one Trip unit.
                                    The rear connector allows the unit to be supplied in two different ways:

                                     Terminals / supply voltage  Frequency  Power input        Inrush current
                                     21,5 ÷ 53 VDC            -            Maximum 10W         Maximum 2 A for 20 ms
                                     105 ÷ 265 VAC/DC         45 ÷ 66 Hz   Maximum 10 VA/W     Maximum 2 A for 20 ms

                                           IMPORTANT: AC and DC supplies cannot be present at the same time

                                    The module provides for 24 VDC auxiliary voltage (terminals 24Vout L+ and L-), which can be used to directly
                                    supply the Trip unit.
                                           WARNING! Ekip Multimeter is sized to supply the Trip unit alone, without additional
                                               modules: if auxiliary voltage is used via module, it must be connected directly
                                           to the terminal box of the CB without the possibility of using Ekip Supply or other
                                           modules

                                    Connections
                                    Belden 3105A cables or equivalent, up to 15 m in length, must be used for the local bus and auxiliary supply.
                                    The cable shield must be earthed on both sides of the connection.
                                    Documents
                                    Further details are available in ABB Library, especially in document 1SDH001000r0520.



       4 - Rc Toroid


                                    Rc is an external differential current sensor which can be installed on Ekip Touch Trip units equipped with Rc
                                    Rating Plug.
                                    When Ekip Touch is being programmed, check in the Settings-Circuit breaker-Ground protection menu to
                                    make sure that the sensor is present (page 46, the configuration menu of the Rc protection parameters must
                                    be activated in the Advanced menu (page 44).

                                           IMPORTANT: the toroid can be choosen as an alternative to the S.G.R. one: protections
                                               Gext, MDGF and Rc are alternatives to each other

                                    Further details about the  Rc toroid connection are available in ABB Library, especially in document
                                    1SDH001000r0521.


       5 - Toroid S.G.R.



                                    |i|S.G.R. or Source Ground Return is an external single-pole current sensor available for LSIG version Ekip
                                    Touch Trip units
                                    When Ekip Touch is being programmed, check in the Settings-Circuit breaker-Ground protection menu to
                                    make sure that the sensor is present (page 46, the configuration menu of the Gext protection parameters
                                    must be activated in the Advanced menu (page 44).
                                           IMPORTANT: the toroid can be choosen as an alternative to the Rc one; protections
                                               Gext, MDGF and Rc are alternatives to each other
                                    Further details about the  S.G.R.  toroid connection are available in ABB Library,  especially  in document
                                    1SDH001000r0507.