Page 238 - Sace Emax 2 Manual for design engineers
P. 238

ABB | SACE Emax 2
        Electrical accessories




       1 - Electrical control accessories



          YO-YC-YO2-YC2 : Opening  The opening coils, YO and YO2, and the closing coil, YC and YC2 , allow the circuit-breaker to be controlled
                         (1)
                                                                                    (1)
                     and closing coil remotely.
                                    The opening of the circuit-breaker is always possible with the circuit-breaker closed, while closing is possible
                                    with the circuit-breaker open and the closing springs charged.
                                    The opening and closing coils can operate in two different modes:
                                     •  instantaneous service (the minimum duration of the command impulse must be 100 ms).
                                     •  service with permanent power supply.


                                                                   D1  C1  C11
                                                                      C3  C13
                                                                   D2  C2  C12
                                                                   YU
                                                                   YO 2  YC  YO

                                    YO-YC-YO2 for E1.2



                                                                 D1  C1  C11  C21
                                                                    C3  C13
                                                                 D2  C2  C12  C22
                                                                 YU
                                                                 YO 2  YC  YO YC 2

                                    YO-YC-YO2-YC2 for E2.2 - E4.2 - E6.2
                                           NOTE: the second opening coil YO2 is alternative to the undervoltage coil YU.

                                           IMPORTANT:
                                            •  If the closing coil is permanently energized and the opening coil trips, after opening,
                                              the closing coil must be momentarily de-energized so that it can be reused for the next
                                              closing operation.
                                            •  If instead the opening coil trips, it is necessary, after having de-energized it, to wait at
                                              least 100 ms before operating the closing coil.
                                    Available voltages and characteristics
                                    The tables listing the available voltages and the electrical characteristics are provided below:
                                     Available voltages (Un)  General characteristics  YO-YO2      YC-YC2  (1)
                                     24 V AC/DC               Operating limits         70...110 %Un  85...110 %Un
                                     30 V AC/DC               Inrush power (Ps)        300 VA/W
                                     48 V AC/DC               Continuous power (Pc)    3.5 VA/W
                                     60 V AC/DC               Maximum opening time     35 ms       -
                                     110…120 V AC/DC          Maximum closing time     -           50 ms
                                     220…240 V AC/DC
                                     240...250 V AC/DC
                                     277 V AC/DC
                                     380…400 V AC
                                     415…440 V AC
                                     480…500 V AC
                                     500…550 V AC

                                    (1)  YC2 not available for E1.2

                                                                                                  Continued on the next page




       236 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                 Electrical accessories | 1 - Electrical control accessories