       2 - Electrical signalling accessories



        AUX 4Q: auxiliary open-closed  The AUX 4Q contacts signal the open/closed state of the circuit-breaker.
                           contacts  These are "switching" contacts and are available in three types:
                                     •  four standard contacts
                                     •  four digital signals (low power)
                                     •  two standard contacts (Q1-Q2) + two digital signals (Q3-Q4)

                                           NOTE: The standard AUX 4Q contacts are always included in the circuit-breakers



                                                            11   21   31  41

                                                            12   22   32  42
                                                            14   24   34  44
                                                            Q1   Q2  Q3   Q4


                                    AUX 4Q for E1.2



                                                          11  21   31  41
                                                          12  22   32  42

                                                          13  23   33  43
                                                         Q1   Q2  Q3   Q4


                                    AUX 4Q for E2.2 - E4.2 - E6.2
                                    The following table provides information on the electrical characteristics:

                                     Characteristics              Standard                        Digital signals
                                                         24V     -                                0.1 A
                                                 DC      125V    0.5A @ 0ms / 0.3A @ 10ms         -
                                                         250V    0.3A @ 0ms / 0.15A @ 10ms        -
                                                                 3A cos  φ 0.3                    -
                                     Breaking
                                     capacity            250V    5A cos  φ 0.7                    -
                                                                 5A cos  φ 1                      -
                                                 AC
                                                                 3A cos  φ 1                      -
                                                         400V    2A cos  φ 0.7                    -
                                                                 1A cos  φ 0.3                    -
                                     Minimum load                100mA @ 24V                      1mA @ 5V


                                    AUX 4Q: Connections
                                    More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
                                    includes the entire circuit diagram 1SDM000091r0001.
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
                                    in particular for E1.2 in the kit sheet  1SDH000999r0601 and for E2.2-E4.2-E6.2 in the kit sheet
                                    1SDH001000r0601.












       240 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                Electrical accessories | 2 - Electrical signalling accessories