Page 242 - Sace Emax 2 Manual for design engineers
P. 242
ABB | SACE Emax 2
2 - Electrical signalling accessories
AUX 4Q: auxiliary open-closed The AUX 4Q contacts signal the open/closed state of the circuit-breaker.
contacts These are "switching" contacts and are available in three types:
• four standard contacts
• four digital signals (low power)
• two standard contacts (Q1-Q2) + two digital signals (Q3-Q4)
NOTE: The standard AUX 4Q contacts are always included in the circuit-breakers
11 21 31 41
12 22 32 42
14 24 34 44
Q1 Q2 Q3 Q4
AUX 4Q for E1.2
11 21 31 41
12 22 32 42
13 23 33 43
Q1 Q2 Q3 Q4
AUX 4Q for E2.2 - E4.2 - E6.2
The following table provides information on the electrical characteristics:
Characteristics Standard Digital signals
24V - 0.1 A
DC 125V 0.5A @ 0ms / 0.3A @ 10ms -
250V 0.3A @ 0ms / 0.15A @ 10ms -
3A cos φ 0.3 -
Breaking
capacity 250V 5A cos φ 0.7 -
5A cos φ 1 -
AC
3A cos φ 1 -
400V 2A cos φ 0.7 -
1A cos φ 0.3 -
Minimum load 100mA @ 24V 1mA @ 5V
AUX 4Q: Connections
More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
includes the entire circuit diagram 1SDM000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
in particular for E1.2 in the kit sheet 1SDH000999r0601 and for E2.2-E4.2-E6.2 in the kit sheet
1SDH001000r0601.
240 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Electrical accessories | 2 - Electrical signalling accessories