Page 243 - Sace Emax 2 Manual for design engineers
P. 243

ABB | SACE Emax 2
                  (1)
          AUX 6Q : Additional open/ The additional AUX 6Q contacts signal the open/closed state of the circuit-breaker.
             closed auxiliary contacts  These are "switching" contacts and are available in three types:
                                     •  six standard contacts
                                     •  six digital signals (low power)
                                     •  three standard contacts (Q1-Q2-Q3) + three digital signals (Q4-Q5-Q6)





                                                       51  61  71  81  91  01
                                                          HC  H1  H2  H3  H4
                                                       52  62  72  82  92  02
                                                          HC  K3  K4  K5  K6
                                                       54  64  74  84  94  04
                                                          HC  K7  K8  K9  K10
                                                       Q5..Q10  EKI PS ignalling 4K

                                     (1)  Only for E2.2 - E4.2 - E6.2
                                           NOTE: it is possible to order the AUX 6 Q contacts only if the circuit-breaker is not equipped
                                               with a protection trip unit with the Ekip Signalling 4K module.
                                    The following table provides information on the electrical characteristics:
                                     Characteristics               Standard                  Digital signals
                                                         24V       -                         0.1 A
                                                  DC     125V      0.5A @ 0ms / 0.3A @ 10ms  -
                                                         250V      0.3A @ 0ms / 0.15A @ 10ms  -
                                                                   3A cos  φ 0.3             -
                                     Breaking            250V      5A cos  φ 0.7             -
                                     capacity
                                                                   5A cos  φ 1               -
                                                  AC
                                                                   3A cos  φ 1               -
                                                         400V      2A cos  φ 0.7             -
                                                                   1A cos  φ 0.3             -
                                     Minimum load                  100mA @ 24V               1mA @ 5V


                                    AUX 6Q: Connections
                                    More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
                                    includes the entire circuit diagram 1SDM000091r0001.
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
                                    particular with the kit sheet 1SDH001000r0601.




































       241 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                Electrical accessories | 2 - Electrical signalling accessories