Page 241 - Sace Emax 2 Manual for design engineers
P. 241

ABB | SACE Emax 2
                           M: Motor The motor automatically recharges the closing springs of the circuit-breaker when these are discharged.
                                    The motor is equipped with a limit contact S33 M/1 that interrupts the power supply of the motor after
                                    charging of the springs is completed.
                                    The motor is equipped with a limit contact S33 M/2 that signals the state of the charged springs.For information
                                    on the S33 M/2 limit contact refer to the dedicated paragraph "S33 M/2: springs charged signalling contact"
                                    in this chapter.






                                                              U1
                                                              U2

                                                              M

                                    M for E1.2






                                                                U1
                                                                U2
                                                                 M


                                    M for E2.2 - E4.2 - E6.2
                                           NOTE: The closing springs can in any case be charged manually through the appropriate
                                               front control lever.
                                    The tables listing the available voltages and the electrical characteristics are provided below:
                                     Available voltages (Un)     General characteristics
                                     24…30 V AC/DC               Operating limits         85...110 %Un
                                     48…60 V AC/DC               Inrush power (Ps)        500 VA/W
                                     100…130 V AC/DC             Power during charge (Pc):  100 VA/W
                                     220…250 V AC/DC             Charging time            Min 5 s, max 10 s
                                     Available voltages (Un)  (1)
                                     380…415 V AC
                                     Available voltages (Un)  (2)
                                     277 V AC/DC
                                     380…400 V AC
                                     440…480 V AC


                                    (1)  for E1.2
                                    (2)  for E2.2 - E4.2 - E6.2
                                    M: Connections
                                    More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
                                    includes the entire circuit diagram 1SDM000091r0001.
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
                                    in particular for E1.2 in the kit sheet  1SDH000999r0609 and for E2.2-E4.2-E6.2 in the kit sheet
                                    1SDH001000r0609.














       239 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                 Electrical accessories | 1 - Electrical control accessories