ABB | SACE Emax 2
                     OV2 Protection Function
                                    OV2 protection functions in the same way as OV protection: the protection sends a TRIP command if one or
                  t                 more line-to-line voltages detected by the unit exceed threshold U16 for longer than t16.
                       U16   OV2    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 93)
                                     •  the graph with trip curve (page 103)
                            t16
                                    Parameters
                                 V   Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the parameters
                                     Enable                                                             OFF
                                                menu
                                                Activates/deactivates transmission of the open command: if disabled, the
                                     Trip Enable                                                        OFF
                                                alarm and exceedance of protection time are only managed as information
                                                Establishes the value that activates the protection.
                                     Threshold   The value is given as both absolute value (Volts) and relative value (Un) and  1,05 Un
                                     U16
                                                can be set within the range:  1 Un to 1.5 Un in 0.001 Un steps
                                                This is the trip time of the protection; the value is given in seconds and can
                                     Time t16                                                           5 s
                                                be set within a range: 0.05 s to 120 s, in 0.01 s steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 83).


          Phase sequence protection The Phase Sequence protection enables an alarm to be activated when the sequence of line-to-line voltages
                                    is not aligned with the sequence set by the user.
                                    The required sequence can be set in the Settings menu and the protection activated in the Advanced menu
                                    (page 46 and page 44).


                      VU Protection Function
                                    The protection trips if the line-to-line voltages read by the unit are unbalanced; the protection sends a TRIP
                  t                 command if the detected unbalance exceeds threshold U14 for longer than t14.
                       U14   VU     The protection excludes itself if the maximum value of the line-to-line voltage is less than 0.3 Un
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                            t14      •  summary table of the protections with the operating characteristics (page 93)
                                     •  the graph with trip curve (page 103)
                                 V  Parameters
                                     Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the parameters
                                     Enable                                                             OFF
                                                menu
                                                Activates/deactivates transmission of the open command: if disabled, the
                                     Trip Enable                                                        OFF
                                                alarm and exceedance of protection time are only managed as information
                                                Establishes the unbalance value that trips the protection.
                                                Unbalance is expressed in percentage value and is calculated in the
                                                following way: % Unba = 100 x (Δmax U ) / U  in range: 2% to 90% in 1%
                                     Threshold   steps.                      mi   mi                    50 %
                                     U14
                                                    NOTE: Δmax U  : maximum deviation among the three voltages
                                                               mi
                                                    calculated by comparing each line-to-line voltage with the mean value;
                                                    U  : mean value of the line-to-line voltages
                                                      mi
                                                This is the trip time of the protection; the value is given in seconds and can
                                     Time t14                                                           5 s
                                                be set within a range: 0.5 s to 60 s, in 0.5 s steps
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 83).