Page 67 - Sace Emax 2 Manual for design engineers
P. 67

ABB | SACE Emax 2
       4 - Voltage Advanced protections



                               List The Advanced Voltage protections, available by default for the Ekip G Touch and Ekip G Hi-Touch models and
                                    configurable in the remaining models as additional SW package, are:
                                     Name           Type of protection                            Page
                                     S(V)           Short-circuit with voltammetric control       65
                                     S2(V)  (1)     Short-circuit with voltammetric control       66
                                     RV             Residual voltage                              68

                                    (1)  S2(V) protection is not available by default with Ekip G Touch. However, it can be integrated by requesting
                                    the relative SW package


                     S(V) Protection Function
                                    S(V) protection protects against short circuits, with a threshold sensitive to the value of the voltage.
                  t                 If the current of one or more phases exceeds threshold I20 for longer than time t20, the protection activates
                       I20    S(V)  and sends a TRIP command.
                                    Threshold I20, after a voltage drop, varies in two different modes:
                            t20      •  Step provides for a stepped variation, depending on parameters Ul and Ks.
                                     •  Lin (linear) provides for a dynamic variation, depending on parameters Ul, Uh and Ks.
                                  I         I                                      I


                                           I20                                    I20



                                      Ks x I20                                Ks x I20




                                                               Ul      V                    UI         Uh     V

                                    Figure 22
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  the summary table of the protections with the calculation formulas (page 93)
                                     •  the graph with trip curve (page 104)
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                  information
                                     Curve        Allows the operating mode, Step or Lin, to be selected  Scal
                                                  Establishes the value that activates the protection and contributes
                                                  towards calculating the trip time.
                                     Threshold I20                                                    1 In
                                                  The value is given as both absolute value (Amperes) and relative value
                                                  (In) and can be set within the range: 0.6 In to 10 In, in 0.1 In steps


                                                                                                  Continued on the next page














       65 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                Ekip Touch - Protections | 4 - Voltage Advanced protections
   62   63   64   65   66   67   68   69   70   71   72