Page 69 - Sace Emax 2 Manual for design engineers
P. 69

Continued from the previous page                                   ABB | SACE Emax 2
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                  information
                                     Curve        Allows the operating mode, Step or Lin, to be selected  Scal
                                                  Establishes the value that activates the protection and contributes
                                                  towards calculating the trip time.
                                     Threshold I21                                                    1 In
                                                  The value is given as both absolute value (Amperes) and relative value
                                                  (In) and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                  It is the voltage that determines the change in trip threshold I21; the
                                                  behavior differs, depending on the mode selected  (1)
                                     Threshold Ul2                                                    1 Un
                                                  The value is given as both absolute value (Volts) and relative value (Un)
                                                  and can be set within the range: 0.2 Un to 1 Un in 0.01 Un steps
                                                  The parameter is shown by the Lin curve and contributes towards I21
                                                  trip threshold calculation:
                                                   • with voltage reading < Uh2 (and ≥ Ul2), the threshold changes
                                     Threshold Uh2  gradually  (1)                                    1 Un
                                                   • with voltage reading ≥ Uh2, the threshold is I21
                                                  The value is given as both absolute value (Volts) and relative value (Un)
                                                  and can be set within the range: 0.2 Un to 1 Un in 0.01 Un steps
                                                  I21 threshold calculation constant.
                                     Threshold Ks2  The value is given as percentage of threshold I21 and can be set   0,6 I21
                                                  within the range: 0.1 I21 to 1 I21, in 0.01 steps
                                                  This is the trip time of the protection.
                                     Time t20     The value is given in seconds and can be set within the range: 0.05 s  0.1 s
                                                  to 30 s, in 0.01 s steps

                                    (1) Trip threshold (depending on the operating curve)


                                     Mode     Voltage reading     Trip threshold
                                              < UI2               Ks2 x I21
                                     Scal
                                              ≥ UI2               I21
                                              < UIs               Ks2 x I21
                                     Lin
                                              ≥ Ul2 (e < Uh2)     ((I21 x ( 1 - Ks2 ) x ( U  - Uh2 ) ) / (Uh2 - Ul2) ) + I21
                                                                                   mis
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 83).

































       67 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                Ekip Touch - Protections | 4 - Voltage Advanced protections