Page 70 - Sace Emax 2 Manual for design engineers
P. 70

ABB | SACE Emax 2
                      RV Protection Function
                                    The protection trips if loss of insulation occurs (verification of residual voltage U0); the protection sends a
                  t                 TRIP command if voltage U0 exceeds threshold U22 for longer than t2.
                       U22   RV     The protection is always available in the 4P configuration.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                            t22      •  summary table of the protections with the operating characteristics (page 93)
                                     •  the graph with trip curve (page 104)
                                 V  Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                  information
                                                  Establishes the value that activates the protection.
                                     Threshold U22  The value is given as both absolute value (Volts) and relative value (Un)  0,15 Un
                                                  and can be set within the range: 0.05 Un to 0.5 Un in 0.001 Un steps
                                                  This is the trip time of the protection; the value is given in seconds and
                                     Time t22                                                         15 s
                                                  can be set within a range: 0.05 s to 120 s, in 0.01 s steps
                                                  This is the time the alarm is retained after the protection has quit the
                                                  alarm condition; it can be useful for keeping the timing activated when
                                     Reset Time   the protection is temporarily deactivated.          0 s
                                                  The value is given in seconds and can be set within the range: 0 s to
                                                  0.2 s, in 0.02 s steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 83).



















































       68 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                Ekip Touch - Protections | 4 - Voltage Advanced protections