ABB | SACE Emax 2
                      OF Protection Function
                                    The protection sends a TRIP command if the grid frequency read by the unit exceeds threshold f13 for longer
                  t                 than t13.
                       f13   OF     The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                            t13      •  summary table of the protections with the operating characteristics (page 93)
                                     •  the graph with trip curve (page 105)
                                 f  Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                  information
                                                  Establishes the value that activates the protection.
                                     Threshold f13  The value is given as both absolute value (Hertz) and relative value (Fn)  1,1 Fn
                                                  and can be set within the range: 1 Fn to 1.1 Fn in 0.001 Fn steps
                                                  This is the trip time of the protection; the value is given in seconds and
                                     Time t13                                                         3 s
                                                  can be set within a range: 0.06 s to 300 s, in 0.01 s steps
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 83).



                     UF2 Protection Function
                                    UF2 protection functions in the same way as UF protection: the protection sends a TRIP command if the grid
                  t                 frequency read by the unit drops below threshold f17 for longer than t17.
                              UF2
                        f17         It is independent of UF protection, thus thresholds and functions of the two protections can be programmed
                                    so as to take advantage of different plant solutions (example: signaling with UF and open command with UF2
                    t17             or vice versa, or both for signaling or tripping).
                                    The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                 f  To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 93)
                                     •  the graph with trip curve (page 105)
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   OFF
                                                  information
                                                  Establishes the value that activates the protection.
                                     Threshold f17  The value is given as both absolute value (Hertz) and relative value (Fn)  0,9 Fn
                                                  and can be set within the range: 0.9 Fn to 1 Fn in 0.001 Fn steps
                                                  This is the trip time of the protection; the value is given in seconds and
                                     Time t17                                                         3 s
                                                  can be set within a range: 0.06 s to 300 s, in 0.01 s steps
                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 83).