                       D Protection Function
                                    D protection is very similar to S protection, with the additional capability of recognizing the direction of the
                  t                 current during a fault.
                       I7     D     The current direction allows the user to find out whether the fault is on the supply side or load side of the
                          t7bw      device controlled by Ekip Touch.
                            t7fw    In ring type distribution systems, D protection allows the distribution section in which the fault has occurred
                                    to be identified and disconnected without affecting the rest of the installation (using zone selectivity).
                                  I  Depending on the direction of the fault, if the current of one or more phases exceeds threshold I7 (I7fw or
                                    I7bw) for longer than time t7 (t7fw or t7bw), the protection activates and sends a TRIP command.
                                    The fault direction is established by comparing the detected fault current with the reference direction.
                                           NOTE: the reference direction is calculated considering the set value of the power flow
                                               direction and the phase sequence (cyclic direction of the phases):

                                                                            Phase sequence     Reference direction
                                     Phase sequence (set) Power flow (set)
                                                                            (detected)         (forward direction)
                                     123                High-->Low          123                High-->Low
                                     123                Bottom --> Top      123                Bottom --> Top
                                     123                High-->Low          321                Bottom --> Top
                                     123                Bottom --> Top      321                High-->Low
                                     321                High-->Low          123                Bottom --> Top
                                     321                Bottom --> Top      123                High-->Low
                                     321                High-->Low          321                High-->Low
                                     321                Bottom --> Top      321                Bottom --> Top

                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  the summary table of the protections with the calculation formulas (page 93)
                                     •  the graph with trip curve (page 106)
                                     Parameter   Description                                              Default
                                                 Activates/deactivates the protection and its availability in the parameters
                                     Enable                                                              OFF
                                                 menu
                                                 Activates/deactivates transmission of the open command: if disabled, the
                                     Trip Enable                                                         ON
                                                 alarm and exceedance of protection time are only managed as information
                                                 Establishes the value that activates the protection with forward direction.
                                     Threshold I7 Fw The value is given as both absolute value (Amperes) and relative value (In)   4 In
                                                 and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                 Establishes the value that activates the protection with backward direction.
                                     Threshold i7   The value is given as both absolute value (Amperes) and relative value (In)   4 In
                                     Bw
                                                 and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                 This is the trip time in the case of forward direction.
                                     Time t7 Fw  The value is given in seconds and can be set within the range: 0.1 s to 0.8   0,2 s
                                                 s, in 0.01 s steps
                                                 This is the trip time in the case of backward direction.
                                     Time t7 Bw  The value is given in seconds and can be set within the range: 0.1 s to 0.8   0,2 s
                                                 s, in 0.01 s steps
                                                 Activates/deactivates the function and selectivity time availability on the
                                     ZoneSelectivity display.

                                     (1)             NOTE: configure selectivities S, S2 OFF to ensure that selectivity D   OFF
                                                     functions correctly, G, Gext and MDGF
                                                 This is the trip time of the protection with the zone selectivity function
                                     Selectivity time  activated, forward direction and selectivity input Fw not present.  0,13 s
                                     Fw  (1)     The value is given in seconds and can be set within the range: 0.1 s to 0.8
                                                 s, in 0.01 s steps
                                                 This is the trip time of the protection with the zone selectivity function
                                     Selectivity time  activated, backward direction and selectivity input Bw not present.  0,13 s
                                     Bw  (1)     The value is given in seconds and can be set within the range: 0.1 s to 0.8
                                                 s, in 0.01 s steps


                                                                                                  Continued on the next page