Continued from the previous page                                   ABB | SACE Emax 2
                                     Parameter   Description                                              Default
                                                 Activates/deactivates the function and availability of the associated
                                     StartUp enable                                                      OFF
                                                 parameters on the display
                                                 Protection threshold valid during Startup time, in the conditions in which the
                                     StartUp     function is activated and with forward current direction .  4 In
                                                                                          (2)
                                     Threshold Fw  (2)  The value is given as both absolute value (Amperes) and relative value (In)
                                                 and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                 Protection threshold valid during Startup time, in the conditions in which the
                                     StartUp     function is activated and with backward current direction.  4 In
                                     Threshold Bw  (2)  The value is given as both absolute value (Amperes) and relative value (In)
                                                 and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
                                                 This is the time for which the StartUp threshold remains activated and is
                                                 calculated from the moment the activation Threshold is exceeded
                                     StartUp Time  (2)                                                   0.1 s
                                                 The value is given in seconds and can be set within the range: 0.1 s to 30 s,
                                                 in 0.01 s steps
                                                 Ekip Touch calculates the phase displacement angle between active and
                                                 apparent power measured: when phase displacement exceeds the set
                                     Direction Min   Direction Min Angle parameter, the unit considers the fault direction to have  3,6 °
                                     Angle
                                                 been identified. The value is given in degrees and can be set within a range
                                                 of 15 values from 3.6° to 69.6°

                                    (1)  details on page 81
                                    (2)  details on page 83

                                    Limitations and additional functions
                                    the functions blocking the type of selectivity and the Trip only Forward and Trip Only Backward parameters
                                    can also be accessed by means of the service connector (via Ekip Connect) or communication via system
                                    bus (page 83).
                                    Notes
                                     •  activation of D directional protection automatically activates the alarm that monitors phase sequence (which
                                       can also be excluded and activated in the manual mode): note how, in the case of a cyclic sequence of
                                       phases that differs from the set value, in the event of a fault the directional protection inverts the reference
                                       direction with respect to the expected direction; details of the phase sequence protection are available
                                       on page 64
                                     •  in the case of small overcurrents, the behavior of the directional protection is influenced by the type of
                                       load: to prevent the direction of the fault current from being incorrectly interpreted in the case of capacitive
                                       loads, it is advisable for the setting of that protection to be made on the basis of real fault conditions and
                                       not overloads







































       74 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                      Ekip Touch - Protections | 6 - Power protections