Continued from the previous page ABB | SACE Emax 2
Parameter Description Default
Activates/deactivates the function and availability of the associated
StartUp enable OFF
parameters on the display
Protection threshold valid during Startup time, in the conditions in which the
StartUp function is activated and with forward current direction . 4 In
(2)
Threshold Fw (2) The value is given as both absolute value (Amperes) and relative value (In)
and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
Protection threshold valid during Startup time, in the conditions in which the
StartUp function is activated and with backward current direction. 4 In
Threshold Bw (2) The value is given as both absolute value (Amperes) and relative value (In)
and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
This is the time for which the StartUp threshold remains activated and is
calculated from the moment the activation Threshold is exceeded
StartUp Time (2) 0.1 s
The value is given in seconds and can be set within the range: 0.1 s to 30 s,
in 0.01 s steps
Ekip Touch calculates the phase displacement angle between active and
apparent power measured: when phase displacement exceeds the set
Direction Min Direction Min Angle parameter, the unit considers the fault direction to have 3,6 °
Angle
been identified. The value is given in degrees and can be set within a range
of 15 values from 3.6° to 69.6°
(1) details on page 81
(2) details on page 83
Limitations and additional functions
the functions blocking the type of selectivity and the Trip only Forward and Trip Only Backward parameters
can also be accessed by means of the service connector (via Ekip Connect) or communication via system
bus (page 83).
Notes
• activation of D directional protection automatically activates the alarm that monitors phase sequence (which
can also be excluded and activated in the manual mode): note how, in the case of a cyclic sequence of
phases that differs from the set value, in the event of a fault the directional protection inverts the reference
direction with respect to the expected direction; details of the phase sequence protection are available
on page 64
• in the case of small overcurrents, the behavior of the directional protection is influenced by the type of
load: to prevent the direction of the fault current from being incorrectly interpreted in the case of capacitive
loads, it is advisable for the setting of that protection to be made on the basis of real fault conditions and
not overloads