                                    Parameters
                                     Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the parameters
                                     Enable                                                             OFF
                                                menu
                                                Activates/deactivates transmission of the open command: if disabled, the
                                     Trip Enable                                                        OFF
                                                alarm and exceedance of protection time are only managed as information
                                                Defines the gradient of the line relating to threshold Q24.
                                     Threshold Kq The value is given as absolute value (slope of the line) and can be set within  -2
                                                the range: -2 to 2 in 0.01 steps
                                                This is the reactive power required to define the trip line and relative TRIP
                                                area
                                     Threshold   The value is given as both absolute value (kVAR) and relative value (Sn) and   0,1 Sn
                                     -Q24       can be set within the range: 0.1 Sn to 1 Sn in 0.001 Sn steps
                                                     NOTE: the threshold expressed in Sn is not preceded by the “-” sign,
                                                    but should still be understood as inverse reactive power
                                                Defines the gradient of the line relating to threshold Q24.
                                     Threshold
                                     Kq2        The value is given as absolute value (slope of the line) and can be set within  2
                                                the range: -2 to 2 in 0.01 steps
                                                Defines the reactive power value at which the protection trips and is
                                                required for the purpose of defining the relative TRIP area
                                     Threshold   The value is given as both absolute value (kVAR) and relative value (Sn) and   0,11 Sn
                                     -Q25       can be set within the range: 0.1 Sn to 1 Sn in 0.001 Sn steps
                                                     NOTE: the threshold expressed in Sn is not preceded by the “-” sign,
                                                    but should still be understood as inverse reactive power
                                                This is the trip time of the protection; the value is given in seconds and can
                                     Time t24                                                           100 s
                                                be set within a range: 0.5 s to 100 s, in 0.1 s steps
                                                This is the minimum activation voltage of the protection. The protection is
                                                not activated if at least one line-to-line voltage value is less than threshold
                                     Threshold   Vmin.                                                  0.5 Un
                                     Vmin
                                                The value is given as both absolute value (Volts) and relative value (Un) and
                                                can be set within the range: 0.5 Un to 1.2 Un in 0.01 Un steps

                                    Limitations and additional functions
                                     •  Ekip Touch accepts parameters in accordance with the following limitations: Q24 < Q25 and Kq < Kq2
                                     •  the block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                       connection to the system bus (page 83).


                    Cos φ Protection The protection activates an alarm when the total Cos φ value drops below the set threshold.
                                    Total cos φ is calculated as ratio between total active Power and total apparent Power.
                                    Parameters
                                    The parameters are available in the Advanced - Signaling menu (page 44)

                                     Parameter  Description                                             Default
                                                Activates/deactivates the protection and availability of the threshold in the
                                     Enable                                                             OFF
                                                menu
                                                Defines the value that activates the protection; can be set within the range:
                                     Threshold                                                          0,95
                                                0.5 to 0.95 in 0.01 steps























       77 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                      Ekip Touch - Protections | 6 - Power protections