       7 - ROCOF protections
                                    The ROCOF Protection package is available by default for Ekip G Hi-Touch and configurable in the remaining
                                    models as additional SW package
                                    The protection is described below:


                  ROCOF Protection Function
                                    ROCOF protection protects against rapid frequency variations: the protection sends a TRIP command if the
                  t                 frequency changes faster than control variation f28 set in the unit for longer than t28.
                       f28    ROCOF

                                                 f(Hz)                        Frequency variation
                            t28                                               after failure (1)

                                                         Frequency fluctuation
                               Hz/s
                                                         (after a failure)
                                                                                           f28
                                                   f mis





                                                                                  t28         t(s)
                                    Figure 25

                                    (1)  example with positive linear variation of the higher frequency of the set f28 value; the protection also
                                    manages negative variations

                                    The protection excludes itself if the maximum value of the line-to-line voltage is less than 30 V.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 93)
                                     •  the graph with trip curve (page 109)
                                    Parameters
                                     Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the parameters
                                     Enable                                                             OFF
                                                menu
                                                Activates/deactivates transmission of the open command: if disabled, the
                                     Trip Enable                                                        OFF
                                                alarm and exceedance of protection time are only managed as information
                                                establishes the maximum admissible frequency variation rate over time; the
                                                protection trips if this rate is exceeded.
                                     Threshold f28                                                      0,6 Hz/s
                                                The value is given as absolute value (Hz/s) Fn) and can be set within the
                                                range: 0.4 Hz/s to 10 Hz/s in 0.2 Hz/s steps
                                                Establishes whether the protection monitors an increase (Up), a decrease
                                     Trip Direction                                                     Up or Down
                                                (Down) or both variations (Up and Down)
                                                This is the trip time of the protection; the value is given in seconds and can
                                     Time f28                                                           0,5 s
                                                be set within a range: 0.06 s to 300 s, in 0.01 s steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 83).



















       78 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                      Ekip Touch - Protections | 7 - ROCOF protections