Page 81 - Sace Emax 2 Manual for design engineers
P. 81
ABB | SACE Emax 2
8 - Protection Adaptive
The Adaptive Protection package is available by default for Ekip Hi-Touch and Ekip G Hi-Touch and
configurable in the remaining models as additional SW package.
The protection is described below:
Dual Set The function enables two different protection configurations to be made, one as an alternative to the other,
by means of a set change with programmable events.
The function can be activated in the Settings-Dual Set menu (page 46)
Parameter Description Default
Enable Activates/deactivates the function OFF
Defines the sets of main and secondary protections (which activate in
Default Set Set A
the presence of the programmed event)
The event that determines set change (from default to secondary) can be programmed in the Advanced -
Functions menu, see the paragraph Programmable Functions and Commands (page 89).
79 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Ekip Touch - Protections | 8 - Protection Adaptive