ABB | SACE Emax 2
                      RC Protection Function
                                    Rc protection protects against the residual current earth faults by detecting the fault current with the
                  t                 appropriate external Rc toroid.
                       Idn    Rc    The protection sends a TRIP command if the current from toroid Rc exceeds threshold Idn for longer than
                                    Tdn.
                             tdn    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 92)
                                  I  •  the graph with trip curve (page 100)
                                    Parameters
                                     Parameter    Description                                         Default
                                                  Defines the value that activates the protection; the value is given in
                                     Threshold Idn                                                    5 A
                                                  Amperes and can be set within a range of values from 3 A to 30 A
                                                  This is the trip time of the protection; the value is given in seconds and
                                     Time Tdn                                                         0,06 s
                                                  can be set within a range of values from 0.05 s to 0.8 s

                                    Limitations and additional functions
                                    Ekip Touch activates and displays the Rc protection parameters if the following conditions are observed:
                                     •  Rating Plug Rc model assembled and installed
                                     •  Measurement enabler with voltage socket module assembled and installed
                                    protection activation includes checking for the presence of toroid Rc and signaling on the diagnosis bar in
                                    the event of alarm/absence