Page 84 - Sace Emax 2 Manual for design engineers
P. 84

Continued from the previous page                                   ABB | SACE Emax 2
                                    Configuration
                                    To correctly configure selectivity D in a ring system:
                                     1. Connect the zone selectivity outputs of each device (example: DFin) to the selectivity input of the same
                                    direction as the device immediately after (example: DFout).
                                     2. Connect all the Szc of devices in the same network together.
                                    Logic table
                                    The table includes all cases in which, with zone selectivity enabled in the device, an alarm condition occurs
                                    or a zone selectivity signal is received from another device.
                                    The Forward output is activated if the fault direction coincides with the reference direction otherwise, if it
                                    is in the opposite direction, the Backward output is activated (page 73)

                                     Fault direc-  Condition         Tripping   Remarks
                                     tion                   DFin  Dbin  Dfout  Dbout  time
                                     Forward   If < I7 Fw  0  x  0  x  No TRIP  Device not in alarm status
                                     Backward  If < I7 Bw  x  0  x  0
                                     Forward   If < I7 Fw  1  x  1  x           The device is not in the alarm status, but
                                                                     No TRIP    sends the selecitivity signal received to the
                                     Backward  If < I7 Bw  x  1  x  1           output of the reference direction
                                     Forward   If > I7 Fw  0  x  1  x  t7 Fw sel  The device is in the alarm status and is the
                                                                                first to detect the fault: trips within time t7 Fw
                                     Backward  If > I7 Bw  x  0  x  1  t7 Bw sel  sel or t7 Bw sel
                                     Forward   If > I7 Fw  1  x  1  x  t7 Fw    The device is in the alarm status but is not the
                                                                                first to detect the fault: trips within time t7 Fw
                                     Backward  If > I7 Bw  x  1  x  1  t7 Bw    (or t7 Bw)


                                           NOTE: when zone selectivity is active and the direction of the fault cannot be established,
                                               the unit trips by considering the first threshold to be exceeded between I7 Fw and I7
                                           Bw, without activating any output (DFout or Dbout).; if both the thresholds have been exceeded
                                           (for example, if they have been set with the same value), the unit trips after the shortest time
                                           between t7 Fw and t7 Bw.



               Trip Only Forward and  D protection can be configured (if available and enabled) with 2  additional parameters via the service
                          Backward connector (via Ekip Connect) or via system bus communication:
                                     •  Trip only Forward: if activated, D protection only controls open commands if forward direction is detected
                                     •  Trip only Backward: if activated, D protection only controls open commands if backward direction is detected
                                    faults in the opposite direction are only handled as alarm information.


                   Type of selectivity The zone selectivity inputs and certain of the outputs can be configured via service connector (via Ekip
                                    Connect) or via system bus communication for protections S, S2, I, G, Gext, MDGF and D (if available and
                                    enabled):
                                     •  Standard: operation as by zone selectivity standard logic (default configuration)
                                     •  Customized: the event that activates the zone selectivity input or output can be selected in this mode.
                                           IMPORTANT: in the Customized configuration, the only zone selectivity activation
                                               event is the one set and standard selectivity operation is therefore not active
                                           (changes should only be made by expert technical personnel).






















       82 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A             Ekip Touch - Protections | 9 - Additional protections and functions