Continued from the previous page                                   ABB | SACE Emax 2
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the function and selectivity time availability on
                                                  the display  (1)
                                                       NOTES :
                                                       • the function is only available with curve t = k
                                     ZoneSelectivity                                                  OFF
                                                       • if both selectivities G and Gext are activated, the input and
                                                     output are shared with the OR function: it is sufficient for even
                                                     only one of the two to be activated to stimulate the inputs and
                                                  outputs
                                                  This is the trip time of the protection with the zone selectivity function
                                                  activated and selectivity input not present  (1)
                                     Selectivity time                                                 0,04 s
                                                  The value is given in seconds and can be set within the range: 0.04 s
                                                  to 0.2 s, in 0.01 s steps
                                                  Activates/deactivates the function and availability of the associated
                                     StartUp enable                                                   OFF
                                                  parameters on the display  (2)
                                                  Protection threshold valid during Startup time, in the conditions in
                                     StartUp      which the function is activated  (2)                0,2 In
                                     Threshold    The value is given as both absolute value (Amperes) and relative value
                                                  (In) and can be set within the range: 0.2 In to 1 In, in 0.1 In steps
                                                  This is the time for which the StartUp threshold remains activated and
                                                  is calculated from the moment the activation Threshold is exceeded  (2)
                                     StartUp Time                                                     0.1 s
                                                  The value is given in seconds and can be set within the range: 0.1 s to
                                                  30 s, in 0.01 s steps

                                    (1)  details on page 80
                                    (2)  details on page83
                                    Limitations and additional functions
                                     •  in the presence of curve t= k/I2, the protection trip time is forced to t41 if the calculation results give a
                                       theoretical value lower than t41 itself
                                     •  Ekip Touch activates and displays Gext protection parameters if the presence of toroid S.G.R has been
                                       enabled in the Settings menu (page 46);protection activation includes checking for the presence of toroide
                                       S.G.R and signaling on the diagnosis bar in the event of alarm/absence
                                     •  the protection is automatically inhibited by the unit if absence of toroid S.G.R is detected
                                     •  the block functions and type of selectivity can also be accessed by means of the service connector (via
                                       Ekip Connect) or communication via system bus (page 82)
                                     •  with CB in UL standard configuration, some parameters have different maximum values: I41 maximum =
                                       1200A, Startup maximum = 1200A, t41 maximum = 400ms


                   MDGF Protection Function
                                    MDGF protection protects against earth faults and detects the fault current with a dedicated toroid MDGF.
                  t                 if MDGF toroid current exceeds threshold I41, the protection trips and, after a time established by the value
                       I41    MDGF
                                    read and by the parameter settings, transmits the TRIP command.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                            t41      •  summary table of the protections with the operating characteristics (page 92)
                                     •  the graph with trip curve (page 101)
                                  I  Parameters
                                    Sensor configuration is available in the Settings menu (page 46)
                                     Parameter    Description                                         Default
                                     External Toroid  It allows the presence of toroid MDGF to be activated  OFF


                                                                                                  Continued on the next page