Page 90 - Sace Emax 2 Manual for design engineers
P. 90

ABB | SACE Emax 2
                  Current thresholds Function
                                    The Current thresholds allow checks to be set along the current lines, to be associated with the programmable
                                    contacts of the Ekip Signalling modules (in all versions).
                                    Two pairs of programmable contacts are available:
                                     •  Threshold 1 I1 and Threshold 2 I1, with control relating to I1
                                     •  Threshold Iw1 and Threshold Iw2, with control relating to In
                                    The thresholds can be enabled and set in the Advanced - Signaling menu (page 44).
                                           IMPORTANT:
                                            •  the current thresholds do not handle the trip, just the signal
                                            •  the function is activated if the trip unit is powered by auxiliary voltage
                                    Parameters
                                     Threshold    Available parameters                                    Default
                                                  Enable: Activates the protection and availability of the threshold in the menu OFF
                                     Threshold 1 I1  Threshold: The value is given in percentage of threshold I1 and can be set
                                                  within the range: 50% I1 to 100% I1, in 1% steps.       50 % I1
                                                  Enable: Activates the protection and availability of the threshold in the menu OFF
                                     Threshold 2 I1  Threshold: The value is given in percentage of threshold I1 and can be set
                                                  within the range: 50% I1 to 100% I1, in 1% steps.       75 % I1
                                                  Enable: Activates the protection and availability of the threshold in the menu OFF
                                                  Direction: allows the user to choose whether to have the signal when the
                                     Threshold Iw1  current is higher (Up) or lower (Down) than the threshold.  Down
                                                  Threshold: The value is given as both absolute value (Amperes) and relative   3 In
                                                  value (In) and can be set within the range: 0.1 In to 10 In, in 0.01 In steps
                                                  Enable: Activates the protection and availability of the threshold in the menu OFF
                                                  Direction: allows the user to choose whether to have the signal when the
                                     Threshold Iw2  current is higher (Up) or lower (Down) than the threshold.  Up
                                                  Threshold: The value is given as both absolute value (Amperes) and relative
                                                  value (In) and can be set within the range: 0.1 In to 10 In, in 0.01 In steps  3 In





























                                    Figure 27

















       88 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A             Ekip Touch - Protections | 9 - Additional protections and functions