Continued from the previous page                                   ABB | SACE Emax 2
                                    Protection configuration is available in the Advanced menu (page 44)
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   ON
                                                  information
                                                  Establishes curve dynamics and the threshold or trip time calculation:
                                     Curve         • t= k: fixed time trip                            t = k
                                                   • t= k/I : inverse time-delay dynamic trip
                                                        2
                                                  Establishes the value that activates the protection and contributes
                                                  towards calculating the trip time.
                                     Threshold I41                                                    0,2 In
                                                  The value is given as both absolute value (Amperes) and relative value
                                                  (In) and can be set within the range: 0.1 In to 1 In, in 0.001 In steps
                                                  It is the trip time or contributes towards timing calculation, depending
                                                  on the type of curve selected.
                                                  The value is given in seconds and can be set within the range:
                                     Time t41      • 0.05 s to 1 s, in 0.05 s steps for t=k           0,4 s
                                                   • 0.1 s to 1 s, in 0.05 s steps for t=k/I  2
                                                       with CB in UL configuration, the maximum settable value of t41
                                                     is 0.4 s
                                                  Warns that the measured current is near to the protection activation
                                                  threshold.
                                                  The value is given in percentage of threshold I1 and can be set within
                                     Threshold I41  the range 50% I41 to 90% I41, in 1% steps.        90 % I41
                                                  The prealarm condition deactivates in two cases:
                                                       • current lower than prealarm threshold I41
                                                       • current higher than threshold I41
                                                  Activates/deactivates the function and selectivity time availability on
                                                  the display  (1)
                                                       NOTES :
                                                       • the function is only available with curve t = k
                                     ZoneSelectivity                                                  OFF
                                                       • if both selectivities G and MDGF are activated, the input and
                                                     output are shared with the OR function: it is sufficient for even
                                                     only one of the two to be activated to stimulate the inputs and
                                                  outputs
                                                  This is the trip time of the protection with the zone selectivity function
                                                  activated and selectivity input not present  (1)
                                     Selectivity time                                                 0,04 s
                                                  The value is given in seconds and can be set within the range: 0.04 s
                                                  to 0.2 s, in 0.01 s steps
                                                  Activates/deactivates the function and availability of the associated
                                     StartUp enable                                                   OFF
                                                  parameters on the display  (2)
                                                  Protection threshold valid during Startup time, in the conditions in
                                     StartUp      which the function is activated  (2)                0,2 In
                                     Threshold    The value is given as both absolute value (Amperes) and relative value
                                                  (In) and can be set within the range: 0.2 In to 1 In, in 0.1 In steps
                                                  This is the time for which the StartUp threshold remains activated and
                                                  is calculated from the moment the activation Threshold is exceeded  (2)
                                     StartUp Time                                                     0.1 s
                                                  The value is given in seconds and can be set within the range: 0.1 s to
                                                  30 s, in 0.01 s steps

                                    (1)  details on page 80
                                    (2)  details on page 83
                                    Limitations and additional functions
                                     •  in the presence of curve t= k/I , the protection trip time is forced to t41 if the calculation results give a
                                                              2
                                       theoretical value lower than t41 itself
                                     •  Ekip Touch activates and displays MDGF protection parameters if the presence of toroid MDGF has been
                                       enabled in the Settings menu (page 46);
                                     •  the block functions and type of selectivity can also be accessed by means of the service connector (via
                                       Ekip Connect) or communication via system bus (page 82)
                                     •  with CB in UL standard configuration, some parameters have different maximum values: I41 maximum =
                                       1200A, Startup maximum = 1200A, t41 maximum = 400ms