Page 86 - Sace Emax 2 Manual for design engineers
P. 86

ABB | SACE Emax 2
                     Gext Protection Function
                                    Gext protection protects against earth faults and detects the fault current with a dedicated external toroid
                  t                 S.G.R.
                       I41    Gext
                                    if S.G.R. toroid current exceeds threshold I41, the protection trips and, after a time established by the value
                                    read and by the parameter settings, transmits the TRIP command.
                            t41     To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 92)
                                  I  •  the graph with trip curve (page 100)
                                    Parameters
                                    Sensor configuration is available in the Settings menu (page 46)
                                     Parameter    Description                                         Default
                                     External Toroid  It allows the presence of external toroid S.G.R. to be activated  OFF
                                                  Allows the reference current of the protection to be selected from
                                                  among four available quantities, from 100 A to 800 A
                                     Toroid size      IMPORTANT: the current selected from the menu must be   100 A
                                                     consistent with the size of the external toroid S.G.R.
                                                  connected to the unit


                                    Protection configuration is available in the Advanced menu (page 44)
                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   ON
                                                  information
                                                  Establishes curve dynamics and the threshold or trip time calculation:
                                     Curve         • t= k: fixed time trip                            t = k
                                                   • t= k/I : inverse time-delay dynamic trip
                                                        2
                                                  Establishes the value that activates the protection and contributes
                                                  towards calculating the trip time.
                                     Threshold I41                                                    0,2 In
                                                  The value is given as both absolute value (Amperes) and relative value
                                                  (In) and can be set within the range: 0.1 In to 1 In, in 0.001 In steps
                                                  It is the trip time or contributes towards timing calculation, depending
                                                  on the type of curve selected.
                                     Time t41                                                         0,4 s
                                                  The value is given in seconds and can be set within the range: 0.1 s to
                                                  1 s, in 0.05 s steps
                                                  Warns that the measured current is near to the protection activation
                                                  threshold.
                                                  The value is given in percentage of threshold I1 and can be set within
                                     Threshold I41  the range 50% I41 to 90% I41, in 1% steps.        90 % I41
                                                  The prealarm condition deactivates in two cases:
                                                       • current lower than prealarm threshold I41
                                                       • current higher than threshold I41


                                                                                                  Continued on the next page

























       84 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A             Ekip Touch - Protections | 9 - Additional protections and functions