Ekip Power Supply
The Ekip Supply module supplies all Ekip trip units and modules present on the Ekip Cartridge or terminal
box of the circuit-breaker with several auxiliary power sources (in AC or DC) available in the switchgear.
The module permits the installation of the other advanced modules. It can be field installed at any time.
Two versions are available according to the control voltage:
• Ekip Supply 110-240V AC/DC 04
• Ekip Supply 24-48V DC
—
Ekip Power Supply
Ekip Link
The Ekip Link module enables the Tmax XT circuit-breaker to be connected to an ABB communication
system. It is available in both inside-breaker and external cartridge versions. It is available as:
• an inside-breaker version for XT2, XT4, and XT5 sizes
• a cartridge and terminal box mounted version for XT2, XT4, XT5, XT7 and XT7 M sizes.
—
Ekip Link
Ekip Com Hub
The Ekip Com Hub is the new communication module for cloud-connectivity. A circuit-breaker
equipped with Ekip Com Hub can establish a connection with an ABB Ability™ Energy and Asset Man-
ager for the low-voltage power distribution panel.
This dedicated module is available in two versions: the inside-breaker (for XT2, XT4 and XT5 sizes) and
the cartridge/ terminal box mounted versions (for XT2, XT4, XT5, XT7 and XT7 M sizes), even when other
modules are present.
—
Ekip Com Hub For further information related to the ABB Ability™ Energy and Asset Manager, please visit the dedi-
cated website at http://new.abb.com/low-voltage/launches/ekip-smartvision.
To ensure cybersecurity of the device, the Ekip Com Hub has loaded a Certificate from a Trusted Autho-
rity. Ekip Com Hub has to be connected to the external network in order to refresh the Cybersecurity
Certificate and have it always up to date. In case of long-term disconnections from the network, more
than 6 months (e.g. module in stock or physically disconnected), the correct functioning of Ekip Com
Hub can be inhibited from the cybersecurity measures in place. It is recommended to keep the module
connected or periodically connect it (e.g. in stock or physically disconnected) to the external network.
Ekip Com Actuator
The Ekip Com Actuator module enables the XT7 M circuit-breakers to be opened and closed remotely.
The Ekip com Actuator is optional and can be ordered for all Ekip Touch trip units equipped with Ekip
Com or Ekip Link modules. The Ekip Com Actuator is installed on the front of the circuit-breaker in the
right-hand accessories area.
—
Ekip Com Actuator