          Accessories for Ekip Touch trip units













                           Protection
                           Ekip Synchrocheck
                           This module enables the control of the synchronism condition when placing two lines in parallel. The
                           module can be used with the Ekip Touch trip units. Ekip Synchrocheck measures the voltages from two
                           phases  of one line through an external transformer and compares them to the voltage values measured at
                           the circuit-breaker. An output contact is available, which is activated upon synchronism, and enables the
                           circuit-breaker to be closed by means of wiring with the closing coil.
                           The Ekip Synchrocheck can be installed in the Ekip Cartridge (for XT2, XT4 and XT5) and in the terminal
                           box (for XT7 and XT7 M).
          —
          Ekip Synchrocheck
                           Output contacts characteristics                         Number of contacts
                           Type                            Monostable              Ekip Synchrocheck
                           Maximum switching voltage       150V DC / 250V AC
                           Maximum switching current
                                          30V DC            2A                     1
                                          50V DC            0.8A                   output
                                          150V DC           0.2A
                                          250V AC           4A
                           Contact/coil insulation         1000 Vrms (1min @50Hz)




                                                                External operating mechanism
                                                                (synchronizing unit or manual
                                                                operating mechanism)  (Phase)
                                                                                      220Vac
                                                Vbar1                                 (Neutral)
                                                                SYNCRO  Supply
                                                       Ekip
                                                       Touch

                                                                     External operating
                                                                     mechanism (synchronizing
                                                                  YC
                                                                     unit or manual operating
                                                                     mechanism)
                                                               Vbar2