COMMUNICATION AND CONNECTIVITY                                                   4/23





















                           Ekip CI
                           This module is an accessory for the Ekip M Touch LRIU trip unit and is needed when the circuit-breaker
                           and the contactor must work in conjunction with each other. In this way the higher number of operations
                           of the contactor are used instead of the circuit-breaker. When the trip unit is set in Normal mode (default
                           mode) by means of the Ekip CI module the contactor is activated in one of the protection trips (excluding
                           I and G protections); if the Heavy mode is set the trip unit directly opens the circuit-breaker. The auto-   04
                           reset function allows the actuation status of the Ekip CI to reset automatically after the contactor has
                           tripped owing to the L function, once an adjustable time from 1 to 1000s has elapsed. Auto-reset can
          —                occur only in Normal mode. The BACK UP function is available and deals with situations whereby an
          Ekip CI
                           opening command transmitted to the contactor via module Ekip CI has not been successful. In this
                           case, the Ekip M Touch LRIU trip unit sends an opening command to the circuit-breaker after waiting a set
                           time Tx. The actuation time of the contactor given by the manufacturer must be considered when the Tx
                           time delay setting is entered. The function is active with an auxiliary supply.

                           Rating Plug
                           The rating plugs are field interchangeable from the front on all the trip units and the protection thresh-
                           olds can be adjusted according to the actual rated current of the system. This function is particularly
                           advantageous in installations that may require future expansion or when the power supplied needs to be
                           limited temporarily (e.g. mobile Gen Set). For the XT7 and XT7 M special rating plugs are also available for
                           residual current protection against ground faults combined with a suitable external toroid. For the XT5,
          —                the following rating plugs are available for the two versions of Ekip Touch (400A and 630A).
          Rating Plug      On the Ekip Touch 400 it is not possible to install the 500A and 630A rating plugs.

                           Nominal Value of the Rating Plug  Ekip Touch 400A     Ekip Touch 630A
                           250A                                                 
                           320A                                                 
                           400A                                                 
                           500A                       -                          
                           630A                       -                          
                            compatible
                           -    not compatible
                           For XT7 and XT7 M the following rating plugs are available
                           Ekip Dip LS/I, Ekip Dip LIG, Ekip M Dip I, Ekip G Dip LS/I
                           Nominal Value              Standard Rating Plug
                           630A                       
                           800A                       
                           1000A                      
                           1250A                      
                           1600A                      
                            compatible

                           Ekip Dip LSI, Ekip Dip LSIG, Ekip Touch all
                           Nominal Value              Standard Rating Plug       Rating Plug for RC protection
                           800A                                                 
                           1000A                                                -
                           1250A                                                
                           1600A                                                -
                            compatible
                           -    not available