Page 170 - SACE Tmax XT - Catalogue
P. 170

7/24             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Signaling













                           Auxiliary Position Contacts – AUP
                           Auxiliary position contacts provide information about the position of the circuit-breaker in relation to
                           the fixed part of plug-in or withdrawable versions.
                           Three types of position contacts (AUPs) are available:
                           • racked-in contact for all plug-in and withdrawable Tmax XT circuit-breakers;
                           • racked-out contact for all withdrawable Tmax XT circuit-breakers;
                           • test contact for withdrawable Tmax XT5, XT6, XT7 and XT7 M circuit-breakers.

                           Circuit-breaker  Max number of    Max number of    Max number of    Max number of AUP
                                            racked-in contacts  test contacts  racked-out contacts
                           XT1  3/4 poles   4                -                -                4
                           XT2  3 poles     2                -                2                4
                                4 poles     4                -                2                6
                           XT3  3/4 poles   4                -                -                4
                           XT4  3/4 poles   4                -                2                6
                           XT5  3/4 poles   3                1                1                5
                           XT6  3/4 poles   3                1                1                5
                           XT7  3/4 poles   2                2                2                6
                           XT7 M 3/4 poles  2                2                2                6


                           Auxiliary position contacts, which provide electrical signaling of the circuit-breaker position in relation to
                           the fixed part, are available in the following versions:

                           AUP          XT1      XT2      XT3      XT4      XT5      XT6      XT7      XT7 M
                           24V DC                                                               
                           250V AC/DC                                                    (1)     (1)
                           400V AC      -        -        -        -        -        -                
                           (1) Same commercial code of AUX 400V