Page 169 - SACE Tmax XT - Catalogue
P. 169

ACCESSORIES                                                                      7/23





















                           Trip auxiliary contact - SY
                           The XT7 circuit-breakers can be equipped with auxiliary contacts that signal that the circuit-breaker is
                           opening due to the intervention of the trip unit, or to the opening of undervoltage/shunt opening re-
                           leases, or to the use of the test button. The contacts are available in the following configurations:
                                                                   400V/250V AC/DC contact  24V DC contact
                           Type                                    Switching             Switching
                           Minimum load                            100mA @ 24V           1mA @ 5V
                           Breaking capacity
                           DC                   24V                -                     0.1A
                                                125V               0.3A                  -
                                                250V               0.15A                 -
                           AC                   250V               12A                   -
                                                400V               3A                    -




                           Contact signaling the tripping of the protection unit Ekip – S51
                           This contact signals the opening of the circuit-breaker after the Ekip protection trip unit has tripped.
                           The contact is available for the XT7 and XT7 M.
                           For the XT7 M circuit-breaker, the closing operation can be carried out only after the “TU Reset” push-
                           button has been restored to its normal operating position. The switching contact can also be associ-
                           ated with an optional accessory for remote resetting - YR.

                                                                     250V AC/DC contact   24V DC contact
                                                                                                                       07
                           Type                                      Switching            Switching
          —                Minimum load                              100mA @ 24V          1mA @ 5V
          Contact signaling the   Breaking capacity
          tripping of the Ekip trip
          unit protection - S51  DC             24V                  -                    0.1A
                                                250V                 0.5A @ 0ms / 0.2A @ 10ms  -
                           AC                   250V                 3A @ cosϕ  0.7       -



                           Contact signaling tripping of the YO2/YU – S52
                           This contact signals that the undervoltage (YU) or the shunt opening release (YO2) have been acti-
                           vated. The contact is the same and depends on the service release mounted in the dedicated position.
                           It is available for the XT7 only, with YU/YO2 installed in the dedicated slot.
                           Auxiliary contact S52 doesn't read the tripping of the YO.

                                                                     250V AC/DC contact   24V DC contact
                           Type                                      Switching            Switching
                           Minimum load                              100mA @ 24V          1mA @ 5V
                           Breaking capacity
                           DC                   24V                  -                    0.1A
                                                250V                 0.5A @ 0ms / 0.2A @ 10ms  -
                           AC                   250V                 3A @ cosϕ  0.7       -