Page 172 - SACE Tmax XT - Catalogue
P. 172

7/26             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Signaling













                           AUP for XT5 and XT6

                           AUP 250V AC - Electrical specifications
                           Power supply voltage  Operating current
                           [V]             L/R = 10 ms                       Resistive load
                           250V AC         -                                 6 A - 5 A (UL/CSA)
                           125V AC         -                                 6 A
                           250V DC         0.2 A                             0.3 A
                           110V DC         0.3 A                             0.45 A
          —
          Auxiliary position
          contact          AUP 24V DC - Electrical specifications
                           Power supply voltage  Operating current
                           [V]             L/R = 10 ms                       Resistive load
                           24V DC          5 A                               5 A

                           AUP for XT7 and XT7 M

                                                                     400V/250V AC/DC contact  24V DC contact
                           Type                                      Changeover contacts  Changeover contacts
                           Minimum load                              100mA @ 24V          1mA @ 5V
                           Breaking capacity
                           DC                   24V                  -                    0.1A
          —
          Auxiliary position                    125V                 0.3A @ 10ms          -
          contacts - AUP
                                                250V                 0.15A @ 10ms         -
                           AC                   250V                 5A @ cosϕ 1          -
                                                                     5A @ cosϕ 0.7        -
                                                                     5A @ cosϕ 0.3        -
                                                400V                 3A @ cosϕ 1          -
                                                                     2A @ cosϕ 0.7        -
                                                                     1A @ cosϕ 0.3        -


                           Early Auxiliary Contacts – AUE
                           Early closing auxiliary contacts: these allow the undervoltage release to be supplied before the main
                           contacts close, in accordance with IEC 60204-1 and VDE 0113 standards.
                           Early opening auxiliary contacts: these allow any electronic devices connected to the system to be dis-
                           connected in advance before the system is damaged by an overvoltage caused by the circuit-breaker
                           opening.
                           The early opening/closing auxiliary contacts can be installed inside the direct and transmitted rotary
          —                handle operating mechanisms for all the SACE Tmax XT family circuit-breakers except for the XT7 (max
          Early Auxiliary Contacts  two contacts @ 400V):
                           •  the cabled version includes 1m long cables (AWG20 cable sections);
                           •  a dedicated code is available in the withdrawable version which includes the connector for the  mov-
                           ing and fixed parts;
                           For the XT7 with a lever operating mechanism, these are mounted directly on the circuit-breaker.

                                        XT1      XT2      XT3      XT4      XT5      XT6      XT7      XT7 M
                           AUE closing                                                          -
                           AUE opening                                  -        -        -        -